Plan Review Notes
Plan Review Notes For Permit 08030365
Permit Number 08030365
Review Stop M
Sequence Number 4
Notes
Date Text
2008-11-02 13:18:41REVIEW #: REVISION
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVISED M-1 SHOWS RETURN AIR TRANSFER DUCTS ELIMINATED
 AND ALL ABOVE CEILING SPACES USED AS PLENUMS. THIS WILL
 CREATE A SITUATION WHERE EXHAUST FANS AND THEIR
 POSITIVELY PRESSURIZED EXHAUST DUCTS WILL BE LOCATED
 WITHIN THE PLENUM SPACE. EXHAUST DUCTS UNDER POSITIVE
 PRESSURESHALL NOT EXTEND INTO OR PASS THROUGH DUCTS OR
 PLENUMS IN ACCORDANCE WITH FBCM 601.3. SHOW HOW THESE
 EXHAUST DUCTS ARE TO BE ISOLATED FROM THE PLENUM IN
 ACCORDANCE WITH THIS SECTION. ALSO, SHOW HOW THE NEWLY
 CREATED PLENUM SPACE WALLS ABOVE THE CEILING ARE TO BE
 FINISHED IN ACCORDANCE WITH FBCM 603.8 AND FBCM 603.9.
  