| Plan Review Notes For Permit 08030365 |
| Permit Number |
08030365 |
|
| Review Stop |
M |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-11-02 13:18:41 | REVIEW #: REVISION | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | REVISED M-1 SHOWS RETURN AIR TRANSFER DUCTS ELIMINATED | | | AND ALL ABOVE CEILING SPACES USED AS PLENUMS. THIS WILL | | | CREATE A SITUATION WHERE EXHAUST FANS AND THEIR | | | POSITIVELY PRESSURIZED EXHAUST DUCTS WILL BE LOCATED | | | WITHIN THE PLENUM SPACE. EXHAUST DUCTS UNDER POSITIVE | | | PRESSURESHALL NOT EXTEND INTO OR PASS THROUGH DUCTS OR | | | PLENUMS IN ACCORDANCE WITH FBCM 601.3. SHOW HOW THESE | | | EXHAUST DUCTS ARE TO BE ISOLATED FROM THE PLENUM IN | | | ACCORDANCE WITH THIS SECTION. ALSO, SHOW HOW THE NEWLY | | | CREATED PLENUM SPACE WALLS ABOVE THE CEILING ARE TO BE | | | FINISHED IN ACCORDANCE WITH FBCM 603.8 AND FBCM 603.9. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|