Plan Review Notes
Plan Review Notes For Permit 08030365
Permit Number 08030365
Review Stop P
Sequence Number 2
Notes
Date Text
2008-05-28 16:10:24DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW: (2ND REVIEW)
  
 1. OK
  
 2. SHT P-1 SANITARY RISER DIAGRAM THE SINKS IN ROOMS
 109 & 110 SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT PER SECTION 909.1.
 ****RESPONSE NOTED, BUT THE SINKS STILL DRAIN THRU THE
 HORIZONTAL WET VENT FOR THE TOILET ROOM. THE LAV IS THE
 VENT FOR THE WATER CLOSET ONLY. (SEE RED LINE
 CORRECTION ON ONE SET OF PLANS).
  
 3. OK
 4. OK
 5. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved