Plan Review Notes
Plan Review Notes For Permit 08030365
Permit Number 08030365
Review Stop M
Sequence Number 2
Notes
Date Text
2008-05-30 10:51:40REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. OK
  
 2. NOT E ON FAN SCHEDULE SAYS ?PROTECT ALL RATED WALLS
 WITH FIRE/SMOKE AS REQUIRED BY CODE.? THIS NOTE IS NOT
 IS NOT SUFFICIENT TO DEMONSTRATE CODE COMPLIANCE. THE
 SPECIFIC LOCATION OF EACH FIRE DAMPER, CEILING DAMPER
 AND SMOKE DAMPER SHALL BE SHOWN AND PROPERLY IDENTIFIED
 ON THE BUILDING PLANS BY THE DESIGNER IN ACCORDANCE
 WITH FBCM 607.8.
  
 3. SIZE OF SOME RETURN AIR FLEX DUCTS STILL MISSING ON
 PLANS. THE TWO MAIN FLEX RETURN DUCTS FROM THE MAIN
 RETURN TRUNK LINE TO THE DOUBLE 24X24 GRILLS IN THE
 HALL DO NOT HAVE A SIZE SHOWN ON PLANS. ALSO, THE
 RETURN FLEX IN CONFERENCE ROOM 106 NOW HAS TWO SIZES.
 IN ONE LOCATION IT IS SHOWN AS 12 INCH AND IN ANOTHER
 IT IS SHOWN AS 8 INCH. WHICH IS CORRECT? PLEASE
 CLARIFY, SHOWING COMPLIANCE WITH FBCM 601.4.
 ADDITIONALLY, MOHS LAB 107 HAS A NOTE FOR 150 CFM. DOES
 THIS APPLY TO THE SUPPLY REGISTER OR THE EXHAUST FAN?
 THE DUCT SIZE FOR THIS SUPPLY REGISTER IS MISSING FROM
 PLANS.
  
 4. OK
  
 5. OK
  
 6. IN MOHS LAB 107 THERE IS AN EXHAUST FAN SHOWN IN THE
 CEILING. IS THIS THE SAME TYPE OF FAN AS EF-1 ON THE
 FAN SCHEDULE OR IS IT A 150 CFM FAN AS THE NOTE ON THE
 FLOOR PLAN INDICATES? WHERE IS THE DUCT FOR THIS FAN
 AND WHAT SIZE IS THE DUCT? SEE COMMENT #2 ABOVE FOR
 ISSUES RELATED TO EXHAUST FAN DUCTWORK.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]