| 2008-06-03 16:26:09 | ** NOTE ADDED: |
| | AS PLANS WERE REVIEWED AND DENIED BY OTHER TRADES SUCH |
| | AS PLUMBING AND MECHANICAL THE 30 DAY PROVISO ISSUED ON |
| | ELECTRICAL SHOULD BE ADDRESSED WHEN PLANS ARE |
| | RESUBMITTED. |
| | THE READINGS SHOULD HAVE ALREADY BE UNDERWAY FROM |
| | LETTER DATED MAY 5TH, 2008 FROM ELECTRICAL CONTRACTOR. |
| | THE DATE OF THIS ELECTRICAL REVIEW IS 6/3/08 AND THIS |
| | 30 DAY WILL MOST CERTAINLY BE DONE BY THE TIME PLANS |
| | ARE RE-SUBMITTED. |
| | PLANS WILL GO INTO A TEMPORARY FAILED STATUS AS OTHER |
| | TRADES HAVE COMMENTS AND PLANS ARE GOING OUT FOR |
| | CORRECTIONS. |
| | ELECTRICAL PLANS ARE ALREADY STAMPED BUT WILL REMAIN |
| | FAILED UNTIL DOCUMENTATION IS SUBMITTED. |
| 2008-06-03 16:17:10 | ** PROVISO/TEMP FAILED** |
| | |
| | |
| | 1) NOTE:AS AGREED BY ELECTRICAL CONTRACTOR AND |
| | CONVERSATION WITH JOHN LOWEN FROM KNIGHT ELECTRIC, |
| | ELECTRICAL LOAD DETERMINATION AS REQUIRED PER 220.87 |
| | WILL BE PROVIDED TO THIS OFFICE WITHIN 30DAYS OF THIS |
| | REVIEW. |
| | THESE SHALL CLEARLY SHOW THE ELECTRICAL LOADS ON |
| | EXISTING PANEL *L3* WITH NEW LOADS BEING ADDED. PLANS |
| | WILL ALSO NEED TO CLARIFY THE LOCATION OF THE EXISTING |
| | PANELS *L3* AND *L3SS*. THESE MAY NOT BE IN OTHER |
| | TENANT SPACE. |
| | PLEASE UNDERSTAND PERMIT MAY BE REVOKED AS PERMITTED BY |
| | THE IN CHAPTER 1 OF THE FLORIDA BUILDING CODE IF |
| | PROVISO IS NOT COMPLIED WITH WITHIN TIME FRAME.. |
| | |
| | THE LETTER SUBMITTED BY THE ELECTRICAL ENGINEER QUOTING |
| | THIS ELECTRICAL REVIEWER COMMENTS DO NOT SEEM TO BE |
| | QUOTING THE PREVIOUS ELECTRICAL REVIEW FOR THIS |
| | PROJECT? |
| | THE WORDING OF THE REVIEW, THE CODE SECTIONS ETC WERE |
| | NOT ON THE REVIEW OF PERMIT #08030365 DATED 3/20/08IT |
| | IS UNCLEAR WHERE THESE NOTES CAME FROM. |
| | IF THE PROVISO AS SET-FORTH ABOVE IS NOT ACCEPTABLE TO |
| | THE DESIGN TEAM THIS OFFICE NEEDS TO BE NOTIFIED BEFORE |
| | PERMIT ISSUANCE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF |
| | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT |
| | HESITATE IN CONTACTING THIS OFFICE. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |