Plan Review Notes
Plan Review Notes For Permit 08030365
Permit Number 08030365
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-11 17:25:55DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA STATUTES
  
 1. SHT P-1 SANITARY RISER DIAGRAM INDICATES THE PIPE
 SIZE AS 2" CONNECTING TO THE STACK AND UP TO THE TOILET
 ROOM. MINIMUM 3" REQUIRED TO THE W/C PER TABLE 709.1.
  
 2. SHT P-1 SANITARY RISER DIAGRAM THE SINKS IN ROOMS
 109 & 110 SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT PER SECTION 909.1.
  
 3. SHT P-1WATER RISER DIAGRAM SHALL SHOW ALL PIPE
 SIZES, AND INDICATE THE LOCATION OF THE CONNECTION TO
 THE WATER MAIN. SECTIONS 106.1.2, 601.1 &604.
  
 4. SHT P-1 THE HUB DRAIN FOR THE P/T AND PAN DRAIN FOR
 THE WATER HEATER SHALL HAVE A TRAP PRIMER. SECTION
 1002.4.
  
 5. DESIGN SHALL BE PER FBC-2004 W/2007 AMENDMENTS.
 PLEASE INDICATE ON PLANS. SECTION 106.1.2 & FS
 533.73(1)(A).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved