2008-03-29 17:05:32REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M-1 PLAN STATES THE HVAC DESIGN IS BY ALTMAN
 BROTHERS, LLC. AN INSTALLING AIR-CONDITIONING
 CONTRACTOR CERTIFIED UNDER CHAPTER 489, FLORIDA
 STATUTES MAY DESIGN AN AIR CONDITIONING SYSTEM UNDER 15
 TONS ONLY IF THIS SYSTEMS SERVES A BUILDING WITH LESS
 THAN 100 OCCUPANTS, THE SYSTEMS HAS INDEPENDENT DUCTS
 AND COSTS LESS THAN $50,000. AS THIS SPACE IS BEING
 SERVED BY A VAV BOX FED BY A LARGER A/C SYSTEM IN A
 BUILDING WITH AN OCCUPANT LOAD GREATER THAN 100, THIS
 SYSTEM IS NOT ELIGIBLE TO BE DESIGNED BY AN AIR
 CONDITIONING CONTRACTOR. THIS PLAN SHALL BE SIGNED AND
 SEALED BY A PROFESSIONAL ENGINEER IN ACCORDANCE WITH
 FBCB 105.3.1.2.
  
 2. M-1: FLOOR PLAN SHOWS 10 INCH ROUND DUCT PENETRATING
 TWO NEW 1-HOUR RATED CORRIDOR WALLS. SHOW HOW THESE
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBCM 607.5 AND 607.1.1.
  
 3. M-1: PROVIDE SIZE OF RETURN AIR FLEX DUCTS TO SHOW
 HOW BALANCED RETURN IS BEING ACHIEVED IN ACCORDANCE
 WITH FBCM 601.4. IF TRANSFER DUCTS ARE NOT DESIGNED TO
 MEET THE EXCEPTIONS UNDER THIS SECTION, A FIELD TEST
 WILL BE REQUIRED AT FINAL INSPECTION TO DETERMINE IF
 PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS ARE AT 0.01
 INCHES WC OR LESS.
  
 4. M-1 FIRE DAMPER DETAIL, NOTE #1: FIRE DAMPERS AND
 SMOKE DAMPERS LOCATED WITHIN AIR DISTRIBUTION AND SMOKE
 CONTROL SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH
 THE REQUIREMENTS OF THIS SECTION, AND THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS AND LISTING
 REGARDLESS OF THE DETAIL ON THE PLANS AS THESE DAMPERS
 ARE PART OF A LISTED AND TESTED ASSEMBLY IN ACCORDANCE
 WITH FBCM 607.2 AND 607.3.
  
 5. THIS WORK IS BEING PROPOSED IN AN EXISTING BUILDING;
 THEREFORE THE DESIGN PROFESSIONAL MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THE FLORIDA EXISTING
 BUILDING CODE IN ACCORDANCE WITH FBCEB 301.5. AS A
 LEVEL OF ALTERATION HAS NOT BEEN DECLARED, FOR THE
 PURPOSE OF THIS REVIEW, IT IS BEING ASSUMED THAT THIS
 IS A LEVEL 2 ALTERATION AS DEFINED IN FBCEB 304.1.
  
 6. M-1: NO INFORMATION WAS PROVIDED REGARDING THE
 TOILET ROOM EXHAUST FAN OR ANY OTHER ASPECT OF
 VENTILATION REQUIREMENTS FOR THIS SPACE. ALL
 RECONFIGURED SPACES INTENDED FOR OCCUPANCY IN ANY WORK
 AREA SHALL BE PROVIDED WITH NATURAL OR MECHANICAL
 VENTILATION OR EXHAUST IN ACCORDANCE WITH THE FBCEB
 609.1. SHOW VENTILATION AND EXHAUST RATES TO BE IN
 COMPLIANCE WITH FBCM SECTION 403.3. PROVIDE OUTSIDE AIR
 CALCULATIONS, INCLUDING OCCUPANCY CLASSIFICATIONS,
 OCCUPANT LOADS, OUTSIDE AIR REQUIRED AND OUTSIDE AIR
 PROVIDED FOR EACH SPACE IN ACCORDANCE WITH FBCM TABLE
 403.3.
  