| 2008-03-20 17:01:32 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE:PLEASE CLARIFY PANELS AND CIRCUITING. PANEL |
| | L3 IS SHOWING A NEW FEED TO NEW PANEL L3A HOWEVER IT IS |
| | UNCLEAR OF THE LOAD OR SIZE OF THE EXISTING PANEL L3 |
| | WITH NEW LOADS BEING ADDED. |
| | PLEASE ALSO SEE THE NEW SPACE IS SHOWING SOME CIRCUITS |
| | COMING FROM EXISTING PANEL L3SS YET IT IS UNCLEAR IF |
| | THE TENANT HAS ACCESS TO THIS PANEL? WHAT DOES THIS |
| | PANEL FEED? OTHER TENANTS? IS IT LOCATED IN ANOTHER |
| | TENANT SPACE? |
| | PLEASE VERIFY LOADS, 220.87 |
| | PLEASE VERIFY LOCATIONS OF ALL OVER CURRENT PROTECTION |
| | DEVICES REQUIRED FOR TENANT 240.24 |
| | |
| | 2) NOTE: PLEASE CLARIFY WHAT THE *SD* IS WHICH IS SHOWN |
| | IN EXAM ROOMS 5 AND 6. |
| | PLEASE VERIFY DEVICES AND THEIR MAXIMUM TIMES. |
| | |
| | COMMENT #2 COULD HAVE BEEN REDLINED AND TO VIF HOWEVER |
| | COMMENT #1 NEEDS TO BE CLARIFIED AND ADDRESSED AT THIS |
| | TIME. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |