 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE SAME COMMENTS FROM THE PREVIOUS REVIEW. SHEET #2 OF
 THE INPUT DATA REPORT ONLY GIVES WATTAGE OF THE
 FIXTURES, NO ALLOWABLE WATTAGES OR COMPARISON
 INDICATING COMPLIANCE.THIS CAN BE ILLUSTRATED ON THE
 PLAN, SHEET E2.
  
 1} 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES,
 GENERAL.
 THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR
 A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING
 SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD
 DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE
 METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF
 INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE
 BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION
 HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR
 LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION
 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING
 POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION
 415.2.C.1 OR 415.2.B.1. THIS CAN BE DEMONSTRATED ON THE
 PLANS INDICATED THE WATTAGES OF THE LUMINAIRES CHOSEN
 FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS.
 PROVIDE SAME.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  