Plan Review Notes
Plan Review Notes For Permit 08030346
Permit Number 08030346
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-25 21:58:30*****DENIED******
  
  
 1.THE ADDRESS, INCLUDING THE SUITE NUMBER, OF THE
 SCOPE OF WORK SITE SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.VERIFYFLAME SPREADS ON THE PRODUCT RATINGS ON
 INTERIOR FINISHES CHART (SHEET AA1) FOR THE LAY-IN
 CEILING, POLOMYX PAINT, AND THE HALLWAY WAINSCOT
 PANELS.INTERIOR WALL AND CEILING FINISH (CLASS A,
 CLASS B, CLASS C.)INTERIOR FLOOR FINISH (CLASS I OR
 CLASS II).
  
 6.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATIFY THE 75' TRAVEL DISTANCE.
  
 7.ON SHEET A5, ONCE A PERSON PASSES THROUGH THE REAR
 EXIT, WHERE DOES ONE GO TO EXIT THE BUILDING.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  