Text |
| 2008-03-25 21:58:30 | *****DENIED****** | | | | | | | | | 1.THE ADDRESS, INCLUDING THE SUITE NUMBER, OF THE | | | SCOPE OF WORK SITE SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET. | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 3.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF EACH SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 5.VERIFYFLAME SPREADS ON THE PRODUCT RATINGS ON | | | INTERIOR FINISHES CHART (SHEET AA1) FOR THE LAY-IN | | | CEILING, POLOMYX PAINT, AND THE HALLWAY WAINSCOT | | | PANELS.INTERIOR WALL AND CEILING FINISH (CLASS A, | | | CLASS B, CLASS C.)INTERIOR FLOOR FINISH (CLASS I OR | | | CLASS II). | | | | | | 6.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATIFY THE 75' TRAVEL DISTANCE. | | | | | | 7.ON SHEET A5, ONCE A PERSON PASSES THROUGH THE REAR | | | EXIT, WHERE DOES ONE GO TO EXIT THE BUILDING. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET | | | EACH COMMENT WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 | | | |
|