| 2008-03-19 16:48:20 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES, | | | GENERAL. | | | THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR | | | A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING | | | SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD | | | DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE | | | METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF | | | INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE | | | BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION | | | HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR | | | LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION | | | 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING | | | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION | | | 415.2.C.1 OR 415.2.B.1. THIS CAN BE DEMONSTRATED ON THE | | | PLANS INDICATED THE WATTAGES OF THE LUMINAIRES CHOSEN | | | FOR THE PROJECT CONFORM TO THE DENSITY REQUIREMENTS. | | | PROVIDE SAME. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|