| 2008-03-24 13:58:00 | BUILDING PLAN REVIEW |
| | PERMIT: 08030346 |
| | ADD: 848 SOUTHERN BLVD. |
| | CONT: PLAN REVIEW |
| | TEL: (561)201-4278 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | |
| | NOTE: THE STATUS OF THIS APPLICATION WILL REMAIN IN THE |
| | FAIL CATEGORY UNTIL A CERTIFIED GENERAL CONTRACTOR IS |
| | SIGNED ON THE APPLICATION. |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4)2004 FBC EXISTING |
| | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE |
| | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO |
| | SECTIONS 303, 304 AND 305 OF THIS CODE. |
| | |
| | 5)PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN |
| | SHOWING ALL CHANGES TO THE EXISTING SPACE. SUBMIT A |
| | WALL LEGEND ON THE DRAWINGS SHOWING THE EXISTING WALLS |
| | AND THE NEW WALLS. STATE THE MATERIALS WHICH WILL BE |
| | USED TO CONSTRUCT THE NEW WALLS. |
| | 6)IF THERE IS A FIRE SPRINKLER SYSTEM IN THE SPACE, |
| | PROVIDE A SPRINKLER PLAN SHOWING HOW THE NEW RENOVATION |
| | WILL AFFECT THE LAYOUT OF THE SPRINKLER HEADS. FBC |
| | 106.3.5.1.1(5) |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | FAX (561) 805-6676 |
| | [email protected] |