| 2008-03-17 14:13:53 | 2004 FBC W/2007 REVISIONS |
| | REPLACE WINDOWS AND DOORS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE VALUE OF THE WORK APPEARS TO BE TOO LOW. THE |
| | VALUE OF THE WORK IS TO INCLUDE THE COST OF THE |
| | MATERIALS PLUS THE COST OF THE LABOR BASED ON WHAT |
| | CONTRACTORS CHARGE FOR THE WORK. REVISE THE VALUE. |
| | |
| | 2) PROVIDE 2 COPIES OF FLOOR PLANS INDICTING THE ROOMS |
| | THAT THE WINDOWS ARE LOCATED IN. WINDOWS IN SLEEPING |
| | ROOMS ARE REQUIRED TO COMPLY WITH EGRESS REQUIREMENTS |
| | AND CAN NOT BE MADE ANY LESS SAFE. 2004 FBC EXISTING |
| | BUILDING SECTION 505.1. |
| | |
| | 3) THE PLANS APPEAR TO SHOW TWO DIFFERENT BUILDINGS. |
| | PLEASE IDENTIFY THE BUILDINGS ON THE PLANS. FBC |
| | 106.1.1* CITY AMENDMENTS. |
| | |
| | 4) THE DRAWINGS STATE BLOCK WINDOWS AT 2 LOCATIONS. ARE |
| | THESE 2 WINDOWS THAT ARE BEING ENCLOSED? PLEASE |
| | CLARIFY. SUBMIT DRAWINGS INDICATING HOW THE OPENINGS |
| | WILL BE ENCLOSED. PROVIDE DETAILS INDICATING EXISTING |
| | WALL CONSTRUCTION AND INFILL MATERIALS AND ATTACHMENTS. |
| | FBC 106.1.1* CITY AMENDMENTS. |
| | |
| | 5) THE 53 X 50-5/8" WINDOW APPEARS TO BE 2 WINDOWS WITH |
| | A STRUCTURAL MULLION BETWEEN THEM. SUBMIT 2 COPIES OF |
| | PRODUCT APPROVALS FOR THE MULLION AS REQUIRED BY DCA |
| | RULE 9B-72. |
| | |
| | 6) THE DRAWINGS SPECIFY A 6' ALUMINUM DOOR. SPECIFY THE |
| | DOOR TYPE ON THE PLANS. IS THIS A SLIDING GLASS DOOR, |
| | DOUBLE FRENCH DOOR OR SOMETHING ELSE?SUBMIT PRODUCT |
| | APPROVALS FOR THIS DOOR AS REQUIRED BY FAC RULE 9B-72. |
| | |
| | 7) SPECIFY THE SWING OF THE DOORS ( INSWING OR OUTSWING |
| | )ON THE PLANS. AND SUBMIT PRODUCT APPROVALS FOR THE |
| | APPROPRIATE SWING. FAC RULE 9B-72. |
| | |
| | 8) SUBMIT 2 COPIES OF ALL PRODUCT APPROVALS. FBC 106.1* |
| | CITY AMENDMENTS |
| | |
| | 9) SUBMIT TWO (2) LEGIBLE COPIES OF THE UPDATED NOA FOR |
| | THE STORM PANELS WITH NOA # 05-0926.02. SUBMIT TWO |
| | COPIES OF A KEY PLAN AND INSTALLATION SCHEDULE FOR THE |
| | STORM PANELS. SPECIFY THE MOUNT TYPE, FASTENER TYPE AND |
| | SPACING, EDGE DISTANCE, SPANS, ETC. SEE ATTACHED SAMPLE |
| | SCHEDULE. FBC 106.1.2* CITY AMENDMENTS |
| | |