| 2008-03-19 09:00:47 | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE SETS OF SUBMITTED PLANS ARE NOT |
| | COMPLETE AT THIS TIME. FOR EXAMPLE: PLEASE SEE COVER |
| | SHEET WHICH LIST THE SHEET A2.1 AND A2.2 FOR REFLECTED |
| | CEILING HOWEVER THESE ARE NOT IN SETS. PLEASE INCLUDE |
| | SHOWING ALL THAT IS EXISTING MEETING. IS THERE ANY |
| | CEILING WORK? |
| | FBC 106.1.2, 106.3.1 FOR ADDITIONAL INFORMATION. |
| | |
| | 2) NOTE: PLEASE SEE ARCHITECTURAL TITLE BLOCKS WHICH |
| | ARE MISSING THE REQUIRED PRINTED NAME AND PRINTED |
| | LICENSE NUMBER OF THE ARCHITECT OF RECORD. |
| | FAC 61G1-16.004, FS 481 |
| | |
| | 3) NOTE: PLEASE SEE NOT ALL THE PANEL SCHEDULE |
| | DESIGNATIONS ON THE RISER DIAGRAM CORRELATE WITH THE |
| | DESIGNATIONS ON THE PANEL SCHEDULES. |
| | PLEASE SEE FOR EXAMPLE: PANELS HP2C, HP2B ETC |
| | PLEASE ALSO SEE THAT PANEL H2C ON E5.0 INDICATES THIS |
| | PANEL AS A 25AMP MLO PANEL WHICH IS NOT POSSIBLE. THIS |
| | PANEL CONTAINS A LOAD HIGHER THAN THE 25AMPS. |
| | AS THIS PANEL DESIGNATION IS NOT ON RISER, CONFIRMATION |
| | ON THIS CAN NOT BE DONE. |
| | PLEASE COORDINATE ALL PANELS. |
| | 240.4, 220, 230 ETC |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 4) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED ON |
| | ELECTRICAL SHEET E5.0 FOR MDP ARE NOT FROM THE CURRENT |
| | 2005 NEC. |
| | PLEASE SEE 220.21 LISTED, HOWEVER THE 2005 NEC DOES NOT |
| | CONTAIN A 220.21. |
| | PLEASE ADJUST AS NEEDED. |
| | FBC 106.1.2 |
| | |
| | ** PLEASE KNOW AS SOME PLANS WERE NOT SUBMITTED AND |
| | SOME SCOPE OF WORK IS NOT CONFIRMED A COMPLETE REVIEW |
| | COULD NOT BE DONE AT THIS TIME. THERE MAY VERY WELL BE |
| | NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |