| 2008-04-01 13:00:58 | BUILDING PLAN REVIEW |
| | PERMIT: 08030318 |
| | ADD: 4400 N. CONGRESS AVE. |
| | CONT: ROBB CONST. INC. |
| | TEL: (561)856-1643 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW:1ST |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER |
| | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE 2007 SUPPLEMENTS. |
| | |
| | 4)PROVIDE FIRE SPRINKLER PLANS SHOWING THE |
| | SPRINKLER-HEAD LAYOUT AND THE EFFECTS OF THE NEW |
| | CONSTRUCTION IN RELATION OF THE EXISTING HEADS. |
| | FBC106.3.5.1.1 (5)* |
| | |
| | 5)61G1-16.004 TITLE BLOCK. |
| | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| | INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| | (2) FIRM LICENSE NUMBER. |
| | (3) NAME OR IDENTIFICATION OF PROJECT. |
| | (4) DATE PREPARED. |
| | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| | THE DOCUMENT. |
| | |
| | 6)WPB AMENDMENTS 106.1.2*ADDITIONAL INFORMATION IS |
| | REQUIRED FOR THE CONSTRUCTABILITY OF WALL TYPE #2 WHICH |
| | IS NOT ATTACHED TO THE STRUCTURE OR CEILING ABOVE AND |
| | HAS AT LEAST SEVEN DOUBLE SOLID CORE DOORS INSTALLED IN |
| | THIS TYPE OF WALL. SEE SHEET A1.1 FOR MORE INFORMATION, |
| | ALSO ON SHEET A1.1 SOME OF THE WALLS ARE MAY BE LABELED |
| | WRONG. |
| | |
| | 7)ARE THE EXISTING WALLS ATTACHED TO THE CEILING OR |
| | STRUCTURE ABOVE? IF THEY ARE ATTACHED TO EITHER |
| | STRUCTURE OR EXISTING CEILING WHY THE NEW INFILL WALLS |
| | WILL BE 4 INCHES BELOW THE CEILING? |
| | |
| | 8)THE PLANS SHALL CLEARLY SHOW THE MEANS OF EGRESS |
| | WHICH SHALL INCLUDE EXIT ACCESS FBC 1013, EXIT FBC 1017 |
| | AND EXIT DISCHARGE FBC 1023. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |