| Plan Review Notes For Permit 08030311 |
| Permit Number |
08030311 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-26 15:19:16 | *****UNSAT***** | | | | | | | | | 1.SPECIFY THE WALL AND CEILING INTERIOR FINISH | | | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. | | | | | | 2.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS | | | I OF CLASS II. | | | | | | 3.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE | | | EXTINGUISHER(S) WHICH SATIFY THE 75' TRAVEL DISTANCE. | | | | | | 4.THE REFLECTED CEILING PLAN (SHEET A3.0) SHOWS AN | | | EXIT/EMERGENCY LIGHT AT THE REAR DOOR.NO SUCH DEVICE | | | IS SHOWN ON SHEET A7.0 | | | | | | 5.PLAN SHOWS A RESTROOM DOOR OPENING/SWINGING INTO | | | THE PATH OF THE REAR EXIT. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE APPROPITE PLAN SHEET | | | EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|