Plan Review Notes
Plan Review Notes For Permit 08030311
Permit Number 08030311
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-26 15:19:16*****UNSAT*****
  
  
 1.SPECIFY THE WALL AND CEILING INTERIOR FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 2.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF CLASS
 I OF CLASS II.
  
 3.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER(S) WHICH SATIFY THE 75' TRAVEL DISTANCE.
  
 4.THE REFLECTED CEILING PLAN (SHEET A3.0) SHOWS AN
 EXIT/EMERGENCY LIGHT AT THE REAR DOOR.NO SUCH DEVICE
 IS SHOWN ON SHEET A7.0
  
 5.PLAN SHOWS A RESTROOM DOOR OPENING/SWINGING INTO
 THE PATH OF THE REAR EXIT.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPITE PLAN SHEET
 EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722