2008-03-19 12:12:58BUILDING PLAN REVIEW
 PERMIT: 08030311
 ADD: 226 CLEMATIS ST.
 CONT: R.A. HEATH CONST.INC.
 TEL: (770)271-8229
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3)ALL THE SHEETS INDICATE EXISTING STORE DESIGN. IF
 THERE ARE CHANGES TO THE EXISTING STORE PLEASE INDICATE
 CLEARLY ON PROPOSED PLANS WHERE THE CHANGES ARE MADE.
 CONSTRUCTION DOCUMENTS SHALL BE ?DIMENSIONED? AND OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THE CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL. FBC. 106.1.1
  
 4)2004 FBC EXISTING 301.5 A DESIGN PROFESSIONAL OR AN
 OWNER MUST ELECT ONE OR A COMBINATION OF LEVELS OF
 ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF
 THIS CODE.
  
 5)SHEET G1.0 MAKES REFERENCE TO THE 2006
 ACCESSIBILITY CODE, THIS IS INCORRECT, AND WE ARE
 PRESENTLY UNDER THE 2004 ACCESSIBILITY CODE VERSION.
  
 6)PLEASE INDICATE IF THERE IS A FIRE SPRINKLER SYSTEM
 INSTALLED AT THIS BUILDING. IF A SPRINKLER SYSTEM IS
 INSTALLED, PROVIDE A SPRINKLER PLAN SHOW THE PLACEMENT
 OF THE SPRINKLER HEADS IN RELATION TO THE RENOVATION
 WALLS. FBC* 106.3.5.1.1(5)
  
 7)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 8)A PORTION OF THE MAIN COUNTER SHALL BE 36 INCHES
 MINIMUM IN LENGTH AND SHALL BE A MAXIMUM OF 36 INCHES
 IN HEIGHT. FBC 11-7 THE ELEVATION DRAWINGS DO NOT SHOW
 THE DIMENSIONS OF THE NEW COUNTERS.
  
 9)FBC 11-4.32.1 FIXED OR BUILT-IN SEATING OR TABLES
 REQUIRED TO BE ACCESSIBLE BY SECTION 11-4.1 SHALL
 COMPLY WITH SECTION 11-4.32. SHOW COMPLIANCE. (SEE
 FIGURE 45)THE EXTERIOR SEATING SHALL HAVE A CLEAR
 PATH OF 44? FOR PEDESTRIANS.
  
 10)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES VALUE SHALL INCLUDE
 STRUCTURAL, ELECTRIC, PLUMBING, INTERIOR FINISH,
 ORCHESTRAL AND DESIGN FEES MARKETING COST AND OVER HEAD
 AND PROFIT EXCLUDING LAND. WPB AMENDMENTS 108.3*
  
 NOTE: PLEASE SHOW ON SEPARATE DRAWINGS AN EXISTING PLAN
 AND A PROPOSED PLAN.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  