Plan Review Notes
Plan Review Notes For Permit 08030275
Permit Number 08030275
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-04-18 10:48:38***DENIED***
  
 PLANS APPEAR TO BE CODE COMPLIANT. PLEASE RESPOND TO
 THE FOLLOWING:
  
 1) THE FLOW TEST DATA IS DATED 7/13/06. IF A MORE
 RECENT TEST WAS PERFORMED, PLEASE PROVIDE THAT
 INFORMATION AS REFERENCED TEST IS GREATER THAN 1 YEAR
 FROM FIRE SPRINKLER SUBMITTAL.
  
 2) FIRE HYDRANT TO BE LOCATED AT A DISTANCE NOT GREATER
 THAN 150' FROM THE FIRE DEPARTMENT CONNECTION. PLEASE
 ILLUSTRATE ON SITE PLAN AND SHOW THE DISTANCE.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756