| 2008-03-18 10:10:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A-1 IS INDICATING A NEW PREP SINK IN KITCHEN, |
| | NEW WATER HEATER AND NEW WASHER. PLEASE KNOW THAT A |
| | PLUMBING PERMIT IS REQUIRED FOR THE PROPOSED WORK. |
| | PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION 105.1 |
| | PERMIT REQUIRED. ANY OWNER, AUTHORIZED AGENT, OR |
| | CONTRACTOR WHO INTENDS TO ERECT, INSTALL, ENLARGE, |
| | ALTER, REPAIR, REMOVE, CONVERT OR REPLACE ANY GAS OR |
| | PLUMBING SYSTEM, THE INSTALLATION OF WHICH IS REGULATED |
| | BY THIS CODE, OR TO CAUSE ANY SUCH WORK TO BE DONE, |
| | SHALL FIRST MAKE APPLICATION TO THE BUILDING OFFICIAL |
| | AND OPTAIN A PERMIT. |
| | |
| | 2.PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE SUBMIT A |
| | PLUMBING SANITARY ISOMETRIC RISER DIAGRAM INDICATING |
| | ALL WASTE, VENTS, TRAPS AND SIZES WITH CLEANOUT |
| | LOCATIONS FOR THE PROPOSED PREP SINK AND WASHER. |
| | |
| | **THE FOLLOWING ARE REQUIREMENTS FOR THE WASHING |
| | MACHINE. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM). |
| | **THE CLEANOUT FOR THE WASHING MACHINE SHALL BE 3". |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4' |
| | A.F.F. |
| | |
| | 3. SHEET A-1 IS INDICATING A NEW WASHER, DRYER, AND |
| | WATER HEATER TO BE INSTALLED IN AN EXISTING GARAGE. |
| | PLEASE INDICATE HOW THESE APPLIANCES WILL BE PROTECTED |
| | FROM DAMAGE BY APPROVED BARRIERS. PER FBC MECHANICAL |
| | SECTION 303.4 PROTECTION FROM DAMAGE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |