| 2008-04-11 07:40:06 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FBC-2004 BUILDING |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. INDICATE THE CODES USED TO DESIGN THE PROJECT. THE |
| | PLANS WILL BE REVIEWED PER THE FLORIDA BUILDING CODE |
| | 2004 EDITION WITH AMENDMENTS UP TO AND INCLUDING THE |
| | 2007 VERSION. SECTION 106.1.2 & FS 553.73(1)(A). PLEASE |
| | INDICATE ON PLANS. |
| | |
| | 2. SHTA-1 PER TABLE 403.1 A SERVICE SINK AND A |
| | DRINKING FOUNTAIN ARE REQUIRED IN EACH TENANT SPACE. |
| | THE WATER COOLER SHOWN ON THE FLOOR PLAN DOES NOT MEET |
| | THE REQUIREMENT FOR A DRINKING FOUNTAIN. SECTION 410.1. |
| | PLEASE SHOW THE LOCATIONS OF THE SERVICE SINKS AND THE |
| | DRINKING FOUNTAINS ON THE FLOOR PLAN, SANITARY RISER |
| | DIAGRAM & THE WATER RISER DIAGRAM. SECTION 403.6. |
| | |
| | 3. SHT A-3 BATHROOM ELEVATIONS. SHOW COMPLIANCE WITH |
| | THE FOLLOWING: |
| | FOR W/C'S |
| | A. 11-4.16.2 CLEAR FLOOR SPACE |
| | B. 11-4.16.3 HEIGHT |
| | C. 11-4.16.4 GRAB BARS (BEHIND W/C) |
| | D. 11-4.16.5 FLUSH CONTROLS |
| | FOR LAVS |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.3 CLEAR FLOOR SPACE |
| | C. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | D. 11-4.19.5 FAUCETS |
| | E. 11-4.19.6 MIRRORS |
| | |
| | 4. SHT A-3 SANITARY RISER DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN. PLEASE SUBMIT A RISER DIAGRAM THAT WOULD |
| | REFLECT THE ACTUAL INSTALLATION. SECTION 106.3.5.1.3. |
| | |
| | 5. SUBMIT A WATER ISOMETRIC RISER DIAGRAM THAT REFLECT |
| | THE FLOOR PLAN. SHOW ALL PIPE SIZES, VALVES ETC. |
| | SECTION 106.3.5.1.3(3)(13). |
| | |
| | 6. PER SECTION 607.1 HOT WATER IS REQUIRED FOR BUILDING |
| | MAINTENANCE. |
| | |
| | 7. SHT A-2 PER SECTION 1503.6 GUTTERS WITH DOWNSPOUTS |
| | ARE REQUIRED ON ALL BUILDINGS WITH EAVES OF LESS THAN 6 |
| | INCHES HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES |
| | OR ON A ROOF ABOVE ANOTHER ROOF. PLEASE INDICATE GUTTER |
| | SIZE AND DOWNSPOUT SIZE AND WELL AS SQUARE FOOTAGE |
| | BEING DRAINED. DOWNSPOUTS SHALL DISCHARGE A MINIMUM 1 |
| | FOOT FROM THE STRUCTRUE SIDEWALLS OF BUILDING. |
| | |
| | 8. INFORMATIONAL: AN IRRIGATION PERMIT AND PLANS ARE |
| | REQUIRED. THIS CAN BE SUBMITTED BY THE IRRIGATION |
| | CONTRACTOR SEPARATELY AFTER BLDG PERMIT IS ISSUED. |
| | SECTION 106.3.5.1.3. |
| | |
| | 9. SHTS L-1 & L-2 THE CERTIFICATE OF AUTHORIZATION, |
| | (FIRM LICENSE), IS REQUIRED IN THE TITLE BLOCK OF THE |
| | LANDSCAPE ARCHITECT PER FAC 61G1_16.004(2) & FS |
| | 481.306. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |