| 2008-04-14 13:49:57 | *****DENIED***** |
| | |
| | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 02.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE |
| | WITH EMERGENCY ACCESS TO THE SAID PROPERTY OR THE |
| | VICINTITY THEREOF (INCLUDING STREETS, ALLEYS, ETC.) . |
| | |
| | 03.SHOW/DISPLAY THE NUMERICAL ADDRESS ON THE |
| | APPROPIATE EXTERIOR ELEVATION WHICH FRONTS 28TH STREET. |
| | AS PER WEST PALM BEACH CODE, THE NUMBERS SHALL BE NO |
| | LESS THAN 6' IN HEIGHT AND NO LESS THAN 1" IN |
| | WIDTH/STROKE. |
| | |
| | 04.IT APPEARS THAT THERE WILL BE FOUR UNITS IN THIS |
| | BUILDING, DISPLAY/SHOW THE UNIT NUMBER AS PER WEST PALM |
| | BEACH CODE OF 3' IN HEIGHT AND 1" IN WIDTH/STROKE. |
| | UNIT NUMBERS SHALL NOT BE ON THE FRONT DOORS.UNIT |
| | NUMBERS MAY BO ON THE REAR DOOR. |
| | |
| | 05.LIST THE HAZARD CLASSIFICATION OF THE CONTENTS AS |
| | LOW, ORDINARY, OR HIGH. |
| | |
| | 06.PLEASE SHOW TRAVEL DISTANCE TO THE EXITS. |
| | |
| | 07.SHOW THE LOCATION OF THE FIRE EXTINGUISHER(S) |
| | WHICH SATIFIES THE 75' TRAVEL DISTANCE. |
| | |
| | 08.PLANS INDICATE THAT THIS IS A NEW ONE STORY |
| | PREFABRICATED METAL BUILDING, WHEREAS IT SHOWN THAT |
| | THIS BUILDING HAS MAXIMUM OF FIVE STORIES.PLEASE |
| | EXPLAIN. |
| | |
| | 09.IT IS STATED THAT THE MAXIMUM NUMBER OF OCCUPANCY |
| | IS 46 PERSONS, IS THIS FOR THE ENTIRE BUILDING OR FOR |
| | EACH UNIT? |
| | |
| | 10.SPECIFY THE INTERIOR WALL AND CEILING FINISH |
| | MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET |
| | EACH COMMENT WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |