| 2008-03-18 16:28:37 | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | |
| | 1) NOTE: ** IMPORTANT**PLEASE SEE THERE ARE NUMEROUS |
| | ITEMS MISSING FOR MINIMUM CODE COMPLIANCE, A FULL AND |
| | COMPLETE REVIEW OF MANY ITEMS COULD NOT BE DONE. THERE |
| | MAY VERY WELL BE SEVERAL NEW COMMENTS ON THE FOLLOWING |
| | REVIEW WHICH CAN NOT BE MADE AT THIS TIME. |
| | FBC 106.3.1, 106.1.2, 106.3.5.1.2 ADMIN SECTIONS FOR |
| | COMPLETE PLANS. |
| | |
| | 2) NOTE: PLEASE SEE THE FOLLOWING CODE SHALL BE STATED |
| | ON PLANS RELEVANT TO THE MINIMUM DESIGNS. PLANS STATE |
| | THE LATEST EDITIONS WHICH IS NOT ACCEPTABLE. PLEASE BE |
| | SURE THE ELECTRICAL AS WELL AS COVER SHEET REFLECTS THE |
| | FOLLOWING REQUIRED FOR THIS TRADE REVIEWER. |
| | FBC 2004 W/2007 REVISIONS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | FBC 106.1.2, FS 553.73 |
| | |
| | 3) NOTE: PLEASE SUBMIT A COMPLETE ELECTRICAL RISER |
| | DIAGRAM SHOWING CODE COMPLIANCE. PLEASE SEE THE |
| | FOLLOWING SUB SECTIONS AS THERE ARE SEVERAL ITEMS |
| | MISSING. |
| | A) PLEASE SEE MISSING REQUIRED GROUNDING ELECTRODE |
| | SYSTEM. FOR EXAMPLE: PLEASE SEE ONE OF THE ITEMS |
| | MISSING IS THE REQUIRED FOOTER STEEL. |
| | B) PLEASE SEE MISSING DISCONNECTS FOR TENANTS. |
| | C) PLEASE SEE MISSING FEEDERS AFTER THE FIRST MEANS OF |
| | DISCONNECT. |
| | D) PLEASE SEE MISSING TAPPED CONDUCTORS. |
| | E) PLEASE SEE MISSING EQUIPMENT GROUNDING CONDUCTOR(S) |
| | AFTER THE FIRST MEANS OF DISCONNECT. |
| | F) PLEASE SEE MISSING CONDUIT TO VERIFY CONDUIT FILL. |
| | G) PLEASE SEE MISSING AIC RATINGS FOR ALL SERVICE |
| | EQUIPMENT. |
| | I) PLEASE SEE MAIN SHOWN AS NEMA 32, WHICH IS NOT |
| | CORRECT. THERE IS NO SUCH LISTING. |
| | J) PLEASE SEE MISSING FLOATING NEUTRAL REQUIRED AT |
| | METERS AFTER THE FIRST MEANS OF DISCONNECT. |
| | K) PLEASE SEE MISSING PANEL SCHEDULES. |
| | L) PLEASE SEE MISSING MINIMUM BRANCH CIRCUIT CONDUCTORS |
| | AND OVER CURRENT PROTECTION(S). |
| | ETC ETC. |
| | 2005 NEC. |
| | 215.5, 110.9, 90.7, 110.3, 250.122, 250.6, 250.66, |
| | 250.50, 240.4, 310.16, 230.70, 240.24, 250.50, 408.4 |
| | ETC |
| | |
| | 4) NOTE: PLEASE SEE THE LOAD CALCULATIONS SUBMITTED DO |
| | NOT REFLECT ANY CALCULATIONS FROM THE NATIONAL |
| | ELECTRICAL CODE. |
| | PLEASE SEE NEC 220. |
| | FBC 106.3.5.1.2 |
| | |
| | 5) NOTE: PLEASE COMPLETE ALL CIRCUITING ON PLANS AND |
| | CORRELATE WITH PANEL SCHEDULES TO BE SUBMITTED. PLEASE |
| | BE SURE TO SEE 700.12F FOR CIRCUITING OF EMERGENCY AND |
| | EXIT LIGHTS. |
| | 310.16, 240.4, 408.4 |
| | FBC 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SEE THE PLANS CALLS FOR 150AMP SERVICE |
| | TO EACH BAY HOWEVER BASED ON THE RISER DIAGRAM THIS ARE |
| | ONLY 100AMPS. |
| | PLEASE CORRELATE ALL. |
| | FBC106.1.2, NEC 215.5, 240.4, 220 ETC |
| | |
| | 7) NOTE: PLEASE SUBMIT ENERGY CALCULATIONS PER FBC |
| | 13-400.3.A, 13-400.3.B,ETC |
| | PLEASE SEE 13-415.2.ABC.1.1, .1.2 AND .1.3, 13-415.2 |
| | FOR INTERIOR ALLOWANCES. |
| | PLEASE SEE MISSING LIGHTING CONTROLS PER |
| | 13-415.1.ABC.1.4 FOR EXTERIOR LIGHTING ETC |
| | AS NO INFORMATION WAS SUBMITTED NO REVIEW OF ANY ITEMS |
| | COULD BE DONE. |
| | PLEASE SEE ALL OF CHAPTER 13 AND COMMENTS FROM OTHER |
| | TRADES.\ |
| | |
| | 8) NOTE: PLEASE SUBMIT PLANS WHICH ARE SIGNED, DATED |
| | AND SEALED BY THE DESIGN PROFESSIONAL. PLEASE SEE ONE |
| | SET SUBMIT HAD THE DESIGNER OF RECORD SIGNATURE |
| | SCRATCHED OUT AND MISSING RAISED SEAL. |
| | PLEASE SEE FAC 61G15-23.002 AND FS471.025 AS EACH |
| | SECTION NOTED REQUIRES BOTH SETS TO BE SIGNED, DATED |
| | AND SEALED BY THE DESIGNER OF RECORD. |
| | |
| | 9) NOTE: PLEASE SEE THE LANDSCAPE ARCHITECTURAL |
| | PLANS/TITLE BLOCKS ARE MISSING THEIR CERTIFICATE OF |
| | AUTHORIZATION NUMBER AS REQUIRED PER FAC 61G1-16.004 |
| | AND FS 481.219. |
| | PLEASE ALSO SEE THE TITLE BLOCKS ARE MISSING THE |
| | REQUIRED PRINTED NAME AND PRINTED LICENSE NUMBER OF |
| | SAID DESIGNER. |
| | ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY |
| | OTHER TRADES. |
| | |
| | ** DUE TO THE EXTENT OF COMMENTS ABOVE, ONE COPY OF |
| | PLANS IS BEING RETAINED BY THIS OFFICE. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |