| Plan Review Notes For Permit 08030216 |
| Permit Number |
08030216 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-04-30 16:58:45 | BUILDING REVIEW . | | | | | | 1- ENERGY CALCULATIONS: | | | A) REVISE WALL INSULATION TO MATCH PLANS. SEE SHEET | | | A-3. | | | B) REVISE RAISED WOOD FLOOR INSULATION TO MATCH | | | PLANS. SEE SHEET A-3. | | | C) REVISE RAISED WOOD FLOOR AREA. SEE PLANS FOR | | | CORRECT AREA. | | | D) REVISE ITEM 10. THIS IS A SINGLE ASSEMBLYNOT | | | UNDER ATTIC AREA. SEE PLANS. | | | E) REVISE OPENING AREA SHOWN ON SHEET #2 TO MATCH | | | PLANS. | | | | | | 2- RESUBMIT PRODUCT APPROVALFOR: | | | A) PRECAST LINTELS.NOA 03-0605.04SUBMITTED IS | | | FOR 4",6" & 12" LINTELS. NEED PRODUCT APPROVAL FOR 8" | | | LINTELS. | | | B) FLAT ROOF.NOA 07-0111.03 IS OK, BUT RAS 117 | | | CALCULATIONS NEED TO BE REVISED. SEE ATTACHED | | | CALCULATIONS. REVISE CALCULATIONS AND RE-SUBMIT PRODUCT | | | APPROVAL. | | | C) GARAGE SWING DOOR. NOA 02-1211.11 SUBMITTED | | | EXPIRED ON FEBRUARY 11, 2008. NEED CURRENT ONE. | | | | | | 3- ARCHITECT TO REVIEW AND APPROVED ALL RE-SUBMITTED | | | PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO FBC | | | 2004. | | | | | | 4- CONTRACTOR TO FOLLOW GEO-TECHNICAL ENGINEER | | | RECOMMENDATIONS TO SUPPORT NEW COLUMNS. SEE SOIL TEST | | | REPORT SUBMITTED. | | | | | | 5- MINIMUM CEILING FAN SIZE REQUIRED IS 56" AS REQUIRED | | | BY TABLE 13-607.1.A.1 FBC 2004. |
|