2008-03-13 10:14:40DENIED;
 1. PLUMBING GENERAL NOTES SHALL BE OF SUFFICIENT
 CLARITY ( CANNOT READ NOTES) SEE FBC-BUILDING CHAPTER 1
 SECTION 106.1.1.
 2. SECONDARY ROOF DRAINS OR SCUPPERS ARE REQUIRED PER
 FBC-PLUMBING TABLE 1106.7 AND SECTION 1107.3.
 3. SANITARY RISER DIAGRAM. THE W/M AND L/T ARE NOT
 PERMITTED ON A SANITARY CROSS AS DRAWN, L/T SHOULD BE
 ABOVE W/M. SEE SECTION 706.3. SHOW THE CLEANOUT ( AT
 THE BOTTOM OF THE STACK) AT 48" AFF.
 4. WATER RISER DIAGRAM; A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE REF. PLEASE SHOW ON DIAGRAM.