Plan Review Notes
Plan Review Notes For Permit 08030216
Permit Number 08030216
Review Stop B
Sequence Number 1
Notes
Date Text
2008-03-17 14:13:05RESIDENTIAL ADDITION, BUILDING REVIEW CHECKLIST. REVIEW
 UNDER FBC 2004 WITH 2007 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT.
 NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK UP.
  
 2- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO
 VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS
 AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- PROPERTY IS LOCATED ON FLOOD ZONE A5 WITH A FLOOD
 ELEVATION OF 7.0'. ELEVATION CERTIFICATE (7.5' MIN.
 ELEVATION) WILL BE REQUIRED PRIOR TO C.O. TO SHOW
 ELEVATION OF ALL EQUIPMENT.
  
 4- SPECIFY LOCATION AND SIZE OF ROOF CROSS VENTILATION
 AS REQUIRED BY SEC. R806 OF 2004 FLORIDA RESIDENTIAL
 CODE.
  
 5- BRING ALL REVISED DRAWINGS FOR HITORIC APPROVAL
 PRIOR TO SUBMITTAL TO THIS OFFICE.
  
 6- CLARIFY WHY LOADING A 2X6 WOOD FRAMED WALL ON AN
 EXISTING 2X4 WOOD FRAMED WALL. PROVIDE ENGINEERING
 CALCULATIONS SHOWING THAT EXISTING 2X4 WALL WILL
 ADEQUATELY SUPPORT 2X6 PROPOSED ADDITION.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 SEC. R301.1 AND TABLE R301.5 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 ALSO, CLARIFY HOW IS THE NEW FOUNDATION GOING TO BE
 INSTALLED IF EXISTING WALLS ARE GOING TO REMAIN?
  
 7-PROVIDE STRUCTURAL DETAILSHOWING ATTACHMENT OF
 STRUCTURAL BUCK TO STEEL COLUMN AND STEEL HEADER FOR
 NEW GARAGE DOOR. SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004 TO VERIFY COMPLIANCE WITH SEC. R301.
  
 8-SHEET A-2:
 A) REVISE LOCATION OF EMERGENCYSCUPPER TO COMPLY
 WITH SEC. R903.4.1.
  
 B) PROVIDE COMPLETE INFORMATION FOR FABRIC AWNINGS
 TO SHOW COMPLIANCE WITH SEC. 3105 FBC 2004 OR APPLY FOR
 SEPARATE PERMIT.
  
 9- SHEET A-4:
 A) REVISE SPECIFICATIONS FOR CEILING TYPE IN GARAGE
 AREA TO COMPLY WITH SEC. R309.2.
  
 B) REVISE SPECIFICATIONS FOR DOUBLE TOP PLATE ON
 EXISTING 2X4 WALL. IT SAYS 2X6 TOP PLATES. REVISE AS
 REQUIRED.
  
 10- SHEET S-1 (SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 TO VERIFY COMPLIANCE WITH SEC. R301):
 A) PROVIDE DETAILS SHOWINGHOWIS THE W8X21 BEAM
 ATTACHED TO THE OTHER W8X21 BEAM AND W8X21 BEAM TO THE
 W12X26 BEAM.
  
 B) TYPICAL EXTERIOR WALL SECTION 5/S-1 DOESN'T
 REFLECT ACTUAL CONDITIONS SHOWN ON THE FRAMING PLAN.
 W8X21 BEAM IS NOT RESTING ON THE STEEL COLUMN AS SHOWN
 ON THE DETAIL.ALSO, STEEL BEAMS ARE NOT SHOWN TO
 SCALE. SIZE OF BEAM SPECIFIED IS NOT THE SAME OF FLOOR
 TRUSSES. REVISE AS REQUIRED.
  
 C) PROVIDE DETAIL/SPECIFICATIONS SHOWING HOWIS THE
 2X6 BOTTOM PLATE ATTACHED TO STEEL BEAM.
  
 D) SPECIFY HOW ARE FLOOR TRUSSES ATTACHED TO STEEL
 BEAMS.WHERE IS JUS-21 TRUSS HANGER BY SIMPSON TAKEN
 FROM?.NEED TO SPECIFY CONNECTOR PROPER FOR STEEL BEAM
 INSTALLATION. SEE SIMPSON CATALOG FOR PROPER CONNECTORS
 TO BE USED.
  
 E) TRELLIS COLUMNS ARE NOT SPECIFIED. WHAT'S WCI?.
 THERE IS NOT INFORMATION ON THE COLUMN SCHEDULE.
  
 F) INFORMATION FOR STEEL COLUMNS IS CONFUSING.
 INFORMATION SHOWN ON DETAIL 4/S-1 AND COLUMN SCHEDULE
 DOESN'T MATCH. REVISE AS REQUIRED AND PROVIDE CLEAR
 SPECS FOR TOPAND BOTTOM PLATES AND ANCHORS. REVISE
 WIDTH AND LENGTH INFORMATION SHOWN ON STEEL COLUMN
 SCHEDULE. IT CAN'T BE 4".
  
 G) NOA 01-0209.03 IS NOT LISTEDIN THE MIAMI
 WEBSITE. REVISE INFORMATION AS REQUIRED.
  
 11- S-2(SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004 TO
 VERIFY COMPLIANCE WITH SEC. R301):
 A) TRUSS ANCHOR SCHEDULE IS NOT CLEAR. BOTH ANCHORS
 ARE MARKED AS "ANCHOR MARK I"AND THERE IS NOT
 REFERENCED ON THE FRAMING PLANS. REVISE AS REQUIRED TO
 CORRELATE TRUSS ANCHOR SCHEDULE WITH FRAMING PLANS.
  
 B) REVISE DISTANCE"A" SPECIFIED ON COMPONENTS &
 CLADDINGDETAIL D.SEE NOTE AT BOTTOM OFFIGURE
 R301.2(8) OF 2004 FLORIDA RESIDENTIAL CODE AND REVISE
 AS REQUIRED.
  
 C) REVISE DETAIL 2/S-2:STEEL BEAM NEEDS TO BE
 DRAWN TO SCALE.(1) THIS BEAM IS NOT 16" DEEP.(2)
 NEED TO DRAW TO SCALE TO SHOW PROPER ATTACHMENT OF
 FLOOR TRUSSES AND TERRACE TRUSSES TO THE BEAM.
 (3) SPECIFY CORRECT TRUSS HANGER FOR PROPOSED
 INSTALLATION TO STEEL BEAM.(4) SPECIFY ATTACHMENT OF
 2X6 BOTTOM PLATE TO STEEL BEAM.
  
 D) BOTTOM PLATEANCHOR TYPE AND SPACING SPECIFIED
 ON DETAIL 6/S-2 DOESN'T MATCH INFORMATION SHOWN ON
 DETAILS 5/S-3, 6/S-3 AND 8/S-3. REVISE AS REQUIRED TO
 MATCH.
  
 E) PROVIDE COMPLETE DETAIL/ SPECIFICATIONS FOR
 ATTACHMENT OF 2X WOOD TO STEEL BEAM SHOWN ON DETAIL
 4/S-2.
  
 F) ALL DETAILS NEED TO INDICATE HOW IS THE2X6
 BOTTOM PLATEFASTENED TOFLOOR TRUSSES AND ROOF
 TRUSSES. SEC.R601.2.
  
 12- SHEET S-3 (SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004
 TO VERIFY COMPLIANCE WITH SEC. R301)
 A) REVISE DISTANCE "A"SHOWING ON DETAIL A. SEE
 NOTE ON FIGURE R301.2(8) OF 2004 FLORIDA RESIDENTIAL
 CODE AND REVISE AS REQUIRED.
  
 B) WINDOW AND DOOR WIND PRESSURES CHART. REVISE ITEM
 D).THIS IS EXPOSURE "C", NOT"B".
 ALSO, REVISE NOTE #1.SEE ITEM 12 A) ABOVE.
  
 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) GARAGE DOORS. NEED PRODUCT APPROVAL FOR DOOR THAT
 MEETS THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT.
  
 B) PRECAST LINTELS.
  
 C) GARAGE SWING DOOR.
  
 D) FLAT ROOF:1) CLEARLY IDENTIFY SPECIFIC APPROVED
 ASSEMBLY TO BE INSTALLED. 2) CLEARLY INDICATE SPECIFIC
 BASE SHEET FASTENING OPTION IF MORE THAN ONE FASTENING
 OPTION IS SHOWN ON SELECTED ASSEMBLY. 3) PROVIDE RAS
 117 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND
 CORNER AREAS AS REQUIRED BY GENERAL LIMITATION #7.
 NOTE: APPROVED ASSEMBLIES WITH GENERAL LIMITATION #9
 ARE NOT GOOD IN THIS AREA BECAUSE NAIL ENHANCING IS NOT
 ALLOWED.
  
 14- ARCHITECT OF RECORD TO REVIEW AND APPROVE IN
 WRITING ALL PRODUCT APPROVALS AS REQUIRED BY SEC.
 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 15- SOIL TEST REPORT :
 A) NEED REPORTWITH ORIGINAL SIGNATURE AND SEAL AS
 REQUIRED BY SEC. 61G15-23.002.
  
 B) NEED TO PROVIDE ENGINEERING FIRM CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED BY SEC.
 61G15-23.002(2).
  
 16- ENERGY CALCULATIONS:
 A) NEED TO USE REVISED FORM 600A-2004 R.
  
 B) PROVIDE COMPLETE INFORMATION ON TOP OF FORM.
  
 C) INSULATION VALUES SHOWN FOR FLOOR, WALLS AND
 CEILING DON'T MATCH. PLANS. REVISE AS REQUIRED TO
 MATCH.
  
 D) CALCULATIONS ARE NOT DONE FOR WORST CASE
 SCENARIO. THEREFORE, BUILDING CORRECT ORIENTATION MUST
 MATCH ACTUAL BUILDING ORIENTATION. REVISE ORIENTATION
 INFORMATION ON SECOND PAGE AS REQUIRED. SEE SURVEYOR
 SITE PLAN FOR CORRECT BUILDING ORIENTATION.
  
 E) OVERHANG LENGTH AND OVERHANG HEIGHT ARE
 INCORRECT. REVISE INFORMATION ON SECOND PAGE AS
 REQUIRED TO MATCH PLANS AND ELEVATIONS.
  
 17- ENERGY CALCULATIONS ARE TAKING THE CEILING FANS
 CREDIT. THEN NEED TO SPECIFY ON PLANS SIZE OF FAN AS
 REQUIRED BY TALE 13-607.1.A.1 OF FBC 2004.
  
 18- OWES $3.84 FOR RADON FEES.
  
 ***NOTE:
 PLEASE RETURN REVIEWED SET OF DRAWINGS AFTER
 CORRECTIONS ARE DONE TO ORIGINAL DRAWINGS TO EXPEDITE
 THE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712
  