| 2008-03-12 13:35:02 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH |
| | SCALE. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION |
| | 106.1.3 QUALITY OF BUILDING PLANS. |
| | |
| | 2. THE CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| | CONFORM TO THE PROVISIONS OF THIS CODE AND RELAVENT |
| | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| | BY THE |
| | BUILDING OFFICIAL. PER CITY OF WPB AMENDMENTS TO |
| | CHAPTER1 SECTION 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 3. THE VALUE SEEMS LOW FOR A 4 H.P. HUSKEY PRO TWO |
| | STAGE COMPRESSOR W/80 GAL. TANK, DRYER SYSTEM, AND |
| | WITHOUT KNOWING HOW MUCH AIR PIPE IS BEING INSTALLED |
| | BECAUSE SUBMITTED PLANS WERE NOT DRAWN TO SCALE |
| | (REFERENCE COMMENT #1). PER CITY OF WPB AMENDMENTS TO |
| | CHAPTER 1, SECTION 108.3 BUILDING PERMIT VALUATION. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |