| Permit Number |
08030131 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-03-24 16:51:17 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.CONCRETE/BLOCK IS SPECIFIED ON THE INSTALLATION | | | SCHEDULE; DOES THIS MEAN CONCETE ON THE TOP, CBS ON THE | | | BOTTOM, OR CONCRETE BLOCK BOTH TOP AND BOTTOM? | | | | | | 2.SEE OPENING 6.11" SPACING IS REQUIRED FOR SPANS | | | BETWEEN 5'8" AND 8', BLOCK SUBSTRATE.12" IS SPECIFIED | | | ON THE INSTALLATION SCHEDULE.PLEASE REVISE AND CHECK | | | ALL OPENINGS AS THIS COMMENT APPLIES TO OTHER | | | OPENINGS. | | | | | | 3.TWO SETS OF DESIGN PRESSURE ENGINEERING WERE | | | SUBMITTED.NONE ARE REQUIRED FOR BUILDINGS UNDER | | | 60FEET, BUT IF YOU WISH TO USE ENGINEERING THAT IS | | | ACCEPTABLE BUT PLEASE ONLY SUBMIT ONE SET, AND CHECK | | | THE INSTALLATION SCHEDULE TO ENSURE THAT THE DESIGN | | | PRESSURES SPECIFIED ARE CONSISTENT WITH THE | | | ENGINEERING. | | | |
|