| 2008-03-24 15:23:51 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | _XX_1.)EFFECTIVE OCTOBER 1, 2007, SECONDARY WATER |
| | BARRIER REQUIRED FS553.844(5)(A). PROVIDE |
| | INFORMATION (PRODUCT APPROVAL OR SPECIFICATIONS) TO |
| | SHOW HOW YOU WILL COMPLY WITH THIS REQUIREMENT. |
| | INFORMATION IS AVAILABLE AT WWW.BOAF.NET, HURRICANE |
| | MITIGATION. |
| | PLEASE PROVIDE THIS INFORMATION FOR THE FLAT DECK. |
| | ***THIRD REQUEST*** |
| | |
| | _XX_5.)FOR THE FLAT ROOF, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO |
| | BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED |
| | ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB |
| | SHEET). |
| | |
| | A LETTER WAS PROVIDED.TWO COMPLETE SETS OF PERMIT |
| | DOCUMENTS REQUIRED.SEE COMMENT #7, THE NOA REQUIRES |
| | ENGINEERING.ALSO NOTE THAT THE LETTER WHICH THE |
| | CONTRACTOR SUBMITTED DOES NOT SPECIFY NUMBER OF ROWS. |
| | |
| | ***THIRD REQUEST - TWO COMPLETE SETS OF PERMIT |
| | DOCUMENTS REQUIRED*** ONLY ONE LETTER PROVIDED. |
| | HOWEVER, SEE ITEM 7 BELOW. |
| | |
| | _XX_ 7.)SEE PRODUCT LIMITATION #7.CALCULATIONS |
| | PREPARED BY AN ARCHITECT, ENGINEER, OR REGISTERED ROOF |
| | CONSULTANT REQUIRED FOR ENHANCED FASTENING. |
| | |
| | ***THIRD REQUEST*** |