| 2008-03-07 15:20:42 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THE VALUE FOR 7 SOLAR PANELS, PIPING, VALVES, |
| | LABOR, DESIGN, AND MIS... COMPONETS SEEMS LOW.PER |
| | FBC-2004, CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | **PROVIDE COPY OF SIGNED CONTRACT BY BOTH PARTIES FOR |
| | TOTAL COST OF JOB. |
| | |
| | 2. ONLY ONE SET OF SOLAR PANEL MANUFACTURER DOCUMENTS |
| | WERE SUBMITTED FOR SUN STAR STR 40, THE OTHER SET WAS |
| | FOR MODEL SR-50. |
| | PER CITY WPB AMENDMENTS TO CHAPTER 1, SECTION 106.1 |
| | SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS, SPECIAL |
| | INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS, AND |
| | OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS WITH |
| | EACH APPLICATION FOR A PERMIT. |
| | |
| | 3. PROVIDE TWO COPIES OF MANUFACTURER'S INSTALLATION |
| | INSTRUCTIONS FOR THE SOLAR PANELS. PER CITY OF WPB |
| | AMENDMENTS TO CHAPTER 1, SECTION 106.1.2 ADDITIONAL |
| | DATA. |
| | |
| | 4. PROVIDE AN ISOMETRIC PIPING RISER DIAGRAM |
| | INDICATING ALL SOLAR PANELS, PIPE SIZES (INDICATE |
| | PIPING MATERIAL TYPE), VALVE LOCATIONS, VACUUM RELIEF |
| | LOCATIONS, PRESSURE AND TEMPERATURE RELIEF VALVE |
| | LOCATION, PROTECTION FROM FREEZING. PER FBC PLUMBING |
| | SECTION 501.1 SCOPE, FBC MECHANICAL SECTION 1401 SCOPE, |
| | 1402 INSTALLATION AND CITY OF WPB AMENDMENTS TO CHAPTER |
| | 1, SECTION 106.1.1 INFORMATION ON CONSTRUCTION |
| | DOCUMENTS. |
| | |
| | 5. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | 6. PER FS 713.13 (1) THRU (6): A NOTICE OF |
| | COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY |
| | COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE |
| | HWY., BEFORE A PERMIT CAN BE ISSUED. PER FS 713.13 (2): |
| | IF THE IMPROVEMENT DESCRIBED IN THE NOTICE OF |
| | COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS |
| | AFTER THE RECORDING THEREOF, SUCH NOTICE IS VOID AND OF |
| | NO FURTHER EFFECT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | END OF COMMENTS: |
| | |