| 2009-04-14 16:16:30 | ** DENIED/PASSED** | | | | | | | | | | | | 1) NOTE: SHEET E-5 OK AND STAMPED. ALL ELECTRICAL | | | SHEETS WERE PLACED IN ONE ROLL WHEN SUBMITTED. TWO | | | COPIES NEED TO GO BACK TO CONTRACTOR. | | | WHEN RESUBMITTING PLANS PLEASE BE SURE TO PLACE SHEETS | | | IN SEPARATE ROLLS/SETS. | | | | | | 2) NOTE: CALLED AND SPOKE TO ENGINEER. FIXTURE *I* | | | MISSING FROM FIXTURE LEGEND AND ENERGY CALCULATIONS. | | | FIXTURES *J* WERE PLACED IN CALCULATIONS BASED ON THE | | | CFL BULB WATTAGE WHEN 13-415.2.ABC.1.1, .1.2 REQUIRES | | | THE RATING OF THE FIXTURE. PLEASE ADJUST CALCULATIONS | | | AND PLANS. | | | THIS WAS GONE OVER ON THE PHONE WITH ENGINEER. THIS | | | WILL BE REVISED ACCORDINGLY AND FIXTURE *I* WILL BE | | | STATED. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|