Plan Review Notes
Plan Review Notes For Permit 08030072
Permit Number 08030072
Review Stop E
Sequence Number 7
Notes
Date Text
2009-04-14 16:16:30** DENIED/PASSED**
  
  
  
 1) NOTE: SHEET E-5 OK AND STAMPED. ALL ELECTRICAL
 SHEETS WERE PLACED IN ONE ROLL WHEN SUBMITTED. TWO
 COPIES NEED TO GO BACK TO CONTRACTOR.
 WHEN RESUBMITTING PLANS PLEASE BE SURE TO PLACE SHEETS
 IN SEPARATE ROLLS/SETS.
  
 2) NOTE: CALLED AND SPOKE TO ENGINEER. FIXTURE *I*
 MISSING FROM FIXTURE LEGEND AND ENERGY CALCULATIONS.
 FIXTURES *J* WERE PLACED IN CALCULATIONS BASED ON THE
 CFL BULB WATTAGE WHEN 13-415.2.ABC.1.1, .1.2 REQUIRES
 THE RATING OF THE FIXTURE. PLEASE ADJUST CALCULATIONS
 AND PLANS.
 THIS WAS GONE OVER ON THE PHONE WITH ENGINEER. THIS
 WILL BE REVISED ACCORDINGLY AND FIXTURE *I* WILL BE
 STATED.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  