| 2009-03-04 14:21:59 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | |
| | 1. SHT P-3 SANITARY RISER DIAGRAM. PLEASE INDICATE THE |
| | VENT TERMINATION POINT FOR THE P-3 SINKS BY THE P-4 |
| | FIXTURES. SECTION 901.1. |
| | |
| | 2. SHT P-3 WATER PIPING DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN AT THE P-3 SINKS BY THE P-4 FIXTURES. |
| | SECTIONS 106.1.1 & 601.1. |
| | |
| | 3. SHT P-3 WATER PIPING DIAGRAM. AIR CHAMBERS ARE NOT |
| | APPROVED. (SHOWN AT ALL FIXTURES). SECTION 604.9 & |
| | PDI-WH 201. PLEASE DELETE. |
| | |
| | 4, SHT P-3 WATER PIPING DIAGRAM SHOWS TWO 1" LINES & |
| | TWO 3/4" INCH LINES WHERE THERE ARE ONLY 3 WATER LINES. |
| | PLEASE CLARIFY. SECTIONS 106.1.1 & 601.1. |
| | |
| | 5. SHT P-3 WATER PIPING DIAGRAM DOES NOT REFLECT THE |
| | FLOOR PLAN. SINK IN THE NAIL SPA IS MOVED TO THE FAR |
| | SIDE OF THE ROOM, BUT THE RISER WAS NOT REVISED TO |
| | REFLECT CHANGE. SECTIONS 106.1.1 & 601.1. PLEASE |
| | CORRELATE. |
| | |
| | 5. SHT P-3 GAS PIPING DIAGRAM. PLEASE SHOW THE REQUIRED |
| | DRIP/SEDIMENT TRAP. SECTIONS 408.2 & 408.4. |
| | |
| | 6. SUBMIT MANUFACTURE SHEETS FOR THE TANKLESS WATER |
| | HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54 & |
| | FBC-2004 FUEL GAS SECTION 402.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |