Plan Review Notes
Plan Review Notes For Permit 08030072
Permit Number 08030072
Review Stop P
Sequence Number 6
Notes
Date Text
2009-03-04 14:21:59DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHT P-3 SANITARY RISER DIAGRAM. PLEASE INDICATE THE
 VENT TERMINATION POINT FOR THE P-3 SINKS BY THE P-4
 FIXTURES. SECTION 901.1.
  
 2. SHT P-3 WATER PIPING DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN AT THE P-3 SINKS BY THE P-4 FIXTURES.
 SECTIONS 106.1.1 & 601.1.
  
 3. SHT P-3 WATER PIPING DIAGRAM. AIR CHAMBERS ARE NOT
 APPROVED. (SHOWN AT ALL FIXTURES). SECTION 604.9 &
 PDI-WH 201. PLEASE DELETE.
  
 4, SHT P-3 WATER PIPING DIAGRAM SHOWS TWO 1" LINES &
 TWO 3/4" INCH LINES WHERE THERE ARE ONLY 3 WATER LINES.
 PLEASE CLARIFY. SECTIONS 106.1.1 & 601.1.
  
 5. SHT P-3 WATER PIPING DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN. SINK IN THE NAIL SPA IS MOVED TO THE FAR
 SIDE OF THE ROOM, BUT THE RISER WAS NOT REVISED TO
 REFLECT CHANGE. SECTIONS 106.1.1 & 601.1. PLEASE
 CORRELATE.
  
 5. SHT P-3 GAS PIPING DIAGRAM. PLEASE SHOW THE REQUIRED
 DRIP/SEDIMENT TRAP. SECTIONS 408.2 & 408.4.
  
 6. SUBMIT MANUFACTURE SHEETS FOR THE TANKLESS WATER
 HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54 &
 FBC-2004 FUEL GAS SECTION 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  