| 2009-02-20 14:38:20 | ** DENIED REVIEW ** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE SEE SHEET E-3. ALL OF THE MANUFACTURE |
| | INFORMATION FOR THE LIGHTING FIXTURES HAS BEEN REMOVED. |
| | THE REVISION IN THE TITLE BLOCK STATES *AS-BUILT*. |
| | HOWEVER REVISIONS FOR THE FINAL INSPECTIONS OF A |
| | PROJECT WOULD NOT REMOVE INFORMATION. IT MAY CHANGE OR |
| | BE REVISED BASED ON A DIFFERENT MANUFACTURE HOWEVER THE |
| | INFORMATION ON THE FINAL RECORD SETS OF PLANS WOULD NOT |
| | BE REMOVED. |
| | PLEASE SEE 13-415.2,13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | SINCE THE CODE REQUIRES THE VA/ WATTAGES TO BE USED ARE |
| | BASED ON THE FIXTURE BALLAST RATINGS ETC AND NOT THE |
| | BULB WATTAGE THE SPECIFIC FIXTURES NEED TO BE LISTED TO |
| | VERIFY CODE COMPLIANCE. |
| | PLEASE SEE THAT THE FACT THE MINIMUM LIGHTING |
| | PERFORMANCE CALCULATIONS WHICH WERE PREVIOUSLY SHOWN ON |
| | E-3 WERE ALSO COMPLETELY REMOVED. |
| | |
| | 2) NOTE: RISER DIAGRAM IS NOW COMPLETELY REVISED |
| | SHOWING A NEW SERVICE TO BE GRANTED BY *SPECIAL |
| | PERMISSION*. |
| | THIS SERVICE IS NOT GRANTED BY 230.2. NO CONTACT TO |
| | THIS OFFICE/REVIEWER HAS BEEN MADE TO GO OVER ANY OF |
| | THESE CHANGES OR PROPOSALS TO DATE. THE SPECIAL |
| | PERMISSION DEFINITIONS IS NOT GRANTED AND NO ADDITIONAL |
| | INFORMATION WAS PROVIDE OR SHOWN FOR CONSIDERATIONS. |
| | SERVICES ARE NOT GRANTED WITHOUT JUSTIFICATION. |
| | THIS WAS IN THE ORIGINAL COMMENTS FROM MARCH 2008 AND |
| | INFORMATION WAS NOT PROVIDED AT THAT TIME EITHER. THE |
| | SERVICE WAS REVISED FOR PERMITTING FROM THE SERVICE |
| | PROVIDED. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |