Plan Review Notes
Plan Review Notes For Permit 08030072
Permit Number 08030072
Review Stop E
Sequence Number 6
Notes
Date Text
2009-02-20 14:38:20** DENIED REVIEW **
  
  
  
 1) NOTE: PLEASE SEE SHEET E-3. ALL OF THE MANUFACTURE
 INFORMATION FOR THE LIGHTING FIXTURES HAS BEEN REMOVED.
 THE REVISION IN THE TITLE BLOCK STATES *AS-BUILT*.
 HOWEVER REVISIONS FOR THE FINAL INSPECTIONS OF A
 PROJECT WOULD NOT REMOVE INFORMATION. IT MAY CHANGE OR
 BE REVISED BASED ON A DIFFERENT MANUFACTURE HOWEVER THE
 INFORMATION ON THE FINAL RECORD SETS OF PLANS WOULD NOT
 BE REMOVED.
 PLEASE SEE 13-415.2,13-415.2.ABC.1.1, .1.2 AND .1.3.
 SINCE THE CODE REQUIRES THE VA/ WATTAGES TO BE USED ARE
 BASED ON THE FIXTURE BALLAST RATINGS ETC AND NOT THE
 BULB WATTAGE THE SPECIFIC FIXTURES NEED TO BE LISTED TO
 VERIFY CODE COMPLIANCE.
 PLEASE SEE THAT THE FACT THE MINIMUM LIGHTING
 PERFORMANCE CALCULATIONS WHICH WERE PREVIOUSLY SHOWN ON
 E-3 WERE ALSO COMPLETELY REMOVED.
  
 2) NOTE: RISER DIAGRAM IS NOW COMPLETELY REVISED
 SHOWING A NEW SERVICE TO BE GRANTED BY *SPECIAL
 PERMISSION*.
 THIS SERVICE IS NOT GRANTED BY 230.2. NO CONTACT TO
 THIS OFFICE/REVIEWER HAS BEEN MADE TO GO OVER ANY OF
 THESE CHANGES OR PROPOSALS TO DATE. THE SPECIAL
 PERMISSION DEFINITIONS IS NOT GRANTED AND NO ADDITIONAL
 INFORMATION WAS PROVIDE OR SHOWN FOR CONSIDERATIONS.
 SERVICES ARE NOT GRANTED WITHOUT JUSTIFICATION.
 THIS WAS IN THE ORIGINAL COMMENTS FROM MARCH 2008 AND
 INFORMATION WAS NOT PROVIDED AT THAT TIME EITHER. THE
 SERVICE WAS REVISED FOR PERMITTING FROM THE SERVICE
 PROVIDED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  