2009-02-23 20:54:45REVIEW #: 1ST REVISION
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 REVISED PAGE M-1 OK AND STAMPED. HOWEVER, THIS REVIEW
 WILL REMAIN IN FAIL STAUS UNTIL THE FOLLOWING COMMENTS
 ARE ADDRESSED:
  
 1. CALCULATIONS PROVIDED BY A STRUCTURAL ENGINEER
 INDICATE THAT THE A/C ROOFTOP PACKAGE UNITS INSTALLED
 ON THIS PROJECT ARE "TEMPSTAR" WHILE THE EQUIPMENT
 SCHEDULE ON PAGE M-2 OF THE PERMIT SET OF PLANS CALLS
 FOR RHEEM EQUIPMENT TO BE INSTALLED. PLEASE REVISE THE
 EQUIPMENT SCHEDULE TO REFLECT THE EQUIPMENT WHICH WAS
 ACTUALLY INSTALLED IN ACCORDANCE WITH FBC-B 106.11 AND
 FBC-M 304.1.
  
 2. THE WIND RESISTANCE CAPABILITIES OF THE "TEMPSTAR"
 EQUIPMENT HAS NOT BEEN ADEQUATELY DEMONSTRATED.
 MECHANICAL EQUIPMENT SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE ANTICIPATED WIND PRESURES IN ACCORDANCE WITH
 FBC-M 301.13. THE STATEMENTS THAT WIND RESISTANCE
 CRITERIA HAVE NOT BEEN "ADOPTED" BY THE PALM BEACH
 COUNTY COMMISSION IS IRRELEVANT. WE ARE NOT IN THE
 JURISDICTION OF THE PALM BEACH COUNTY COMMISSION AND
 THE FLORIDA BUILDING CODE (FBC) IS A STATE WIDE
 MANDATED MINIMUM CODE. NO LOCAL JURISDICTION HAS THE
 AUTHORITY TO MAKE THE FBC MORE OR LESS STRINGENT. ALSO,
 THERE IS NO BASIS IN CODE FOR THE ENGINEER'S STATEMENT
 THAT ALL STRUCTURES UNDER 35 FEET IN HEIGHT ARE EXEMPT
 FROM WIND RESISTANCE REQUIREMENTS. ALL BUILDINGS,
 REGARDLESS OF HEIGHT, CONSTRUCTED IN THE STATE OF
 FLORIDA ARE SUBJECT TO THE WIND RESISTANCE PROVISIONS
 OF THE FBC. IN ORDER TO DEMONSTRATE CODE COMPLIANCE FOR
 THE EQUIPMENT BEING INSTALLED ON THIS PROJECT, PLEASE
 USE ONE OF THE FOLLOWING METHODS:
  
 A) PROVIDE SUPPORTING DOCUMENTATION FROM THE EQUIPMENT
 MANUFACTURER SHOWING THAT THESE UNITS ARE DESIGNED AND
 WILL WITHSTAND THE ANTICIPATED WIND PRESSURES AS
 CALCULATED IN ACCORDANCE WITH FBC-B SECTION 1609.
  
 B) PROVIDE A RATIONAL ANALYSIS OF THE CONSTRUCTION OF
 THE EQUIPMENT SHOWING THESE UNITS WILL WITHSTAND THE
 ANTICIPATED WIND PRESSURES AS CALCULATED IN ACCORDANCE
 WITH FBC-B SECTION 1609.
  
 FOR ADDITIONAL INFORMATION REGARDING WIND RESISTANCE
 REQUIREMENTS FOR MECHANICAL EQUIPMENT AND APPLIANCES,
 PLEASE SEE THE DECLARATORY STATEMENT FROM THE FLORIDA
 BUILDING COMMISSION DCA08-DEC205. A COPY IS ATTACHED TO
 THESE COMMENTS FOR YOUR CONVENIENCE.
  
 NOTE: DOCUMENTATION WAS PREVIOUSLY PROVIDED FOR THE
 RHEEM EQUIPMENT ORIGINALLY PROPOSED FOR THIS PROJECT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]