Plan Review Notes
Plan Review Notes For Permit 08030072
Permit Number 08030072
Review Stop E
Sequence Number 4
Notes
Date Text
2008-08-01 13:04:53** NOTE ADDED
  
 SPOKE TO JOHN FROM T&F 12:57PM ON 8/1/08HE WILL BRING
 IN CALCULATIONS ON MONDAY THE 7TH SO THEY MAY BE
 REVIEWED.
2008-08-01 11:49:48** TEMP DENIED ***
  
 1) NOTE: NO NEW ENERGY CALCULATIONS SUBMITTED ONLY THE
 OLD ARE IN PACKAGE. CALLED JOHN FROM T&F CONTRACTORS TO
 HAVE THE CALCULATIONS BROUGHT IN TOBE REVIEWED.
 ELECTRICAL PLANS ARE OK HOWEVER STILL NEED TO REVIEW
 CALCULATIONS FOR *MINIMUM* CODE COMPLIANCE WITH
 13-415.2.ABC.1.1,.1.2.
 CONTRACTOR SAID ON PHONE HE WILL CALL BACK AS HE WAS IN
 A MEETING AND COULD NOT TALK. ROUTED TO OTHER TRADES
 FOR THEIR FINAL REVIEW/STAMPING AND PROCESSING OF
 PLANS.
  
 IF THERE ARE QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH