2008-07-17 14:03:18** DENIEDRE-SUB FOR PLAN REVIEW ONLY**
  
  
  
 1) NOTE: PLANS HAVE STILL ONLY BEEN SUBMITTED FOR PLAN
 REVIEW AND HAVE NOT YET BEEN SUBMITTED FOR PERMIT.
  
 2) NOTE: PLEASE KNOW THIS IS THE FIRST TIME ENERGY
 CALCULATIONS ARE BEING SUBMITTED FOR REVIEW.THIS
 REVIEWER HAS CALLED ENGINEER OF RECORD AND GONE OVER
 ITEMS. NOTES WERE BEING TYPED AT THE TIME OF
 CONVERSATION WITH THE DESIGN PROFESSIONAL.
 PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS ARE IN
 NEED OF REVISING TO MEET COMPLIANCE WITH FBC
 13-400.3.B, 13-415.2, 13-415.2.ABC.1.1 AND .1.2. PLEASE
 SEE THE ELECTRICAL PLANS CONTAIN LIGHTING FIXTURES
 WHICH ARE NOT IN THE INPUT DATA REPORT. THE INPUT DATA
 REPORT WILL BE NOTED AS IDR FOR THE REMAINDER OF THIS
 COMMENT.
 PLEASE SEE THE PLANS AS THE LIGHTING PERFORMANCE
 CALCULATIONS SHOWN DO NOT COORDINATE WITH THE SUBMITTED
 CALCULATIONS. THE LIGHTING PERFORMANCE CALCULATIONS ON
 PLANS DO NOT NEED TO BE THERE IF COMPLIANCE IS GOING TO
 BE SHOWN IN THE METHOD *B* CALCULATIONS.
 ** SOME EXAMPLES OF THESE ARE GIVEN BELOW.
  
 FOR EXAMPLE:
 PLANS SHOW A TOTAL OF 20 108W FIXTURES YET THE IDR ONLY
 CONTAINS 17 OF THESE.
  
 FOR EXAMPLE:
 PLEASE SEE THE FIXTURE *J* AS SHOWN ON PLANS AND ON
 FIXTURE LEGEND IS A 26WATT FIXTURE. PLANS SHOW 4 OF
 THESE AND YET THE IDR DO NOT SHOW ANY 26WATT FIXTURES.
  
 FOR EXAMPLE:
 PLEASE SEE PLANS INDICATE *L* FIXTURES WHICH ARE SHOWN
 AS 50W FIXTURES YET THE IDR DOES NOT CONTAIN ANY 50WATT
 FIXTURES.
  
 ** PLEASE COORDINATE ALL OF THE ABOVE.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  