| 2008-07-17 14:03:18 | ** DENIEDRE-SUB FOR PLAN REVIEW ONLY** |
| | |
| | |
| | |
| | 1) NOTE: PLANS HAVE STILL ONLY BEEN SUBMITTED FOR PLAN |
| | REVIEW AND HAVE NOT YET BEEN SUBMITTED FOR PERMIT. |
| | |
| | 2) NOTE: PLEASE KNOW THIS IS THE FIRST TIME ENERGY |
| | CALCULATIONS ARE BEING SUBMITTED FOR REVIEW.THIS |
| | REVIEWER HAS CALLED ENGINEER OF RECORD AND GONE OVER |
| | ITEMS. NOTES WERE BEING TYPED AT THE TIME OF |
| | CONVERSATION WITH THE DESIGN PROFESSIONAL. |
| | PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS ARE IN |
| | NEED OF REVISING TO MEET COMPLIANCE WITH FBC |
| | 13-400.3.B, 13-415.2, 13-415.2.ABC.1.1 AND .1.2. PLEASE |
| | SEE THE ELECTRICAL PLANS CONTAIN LIGHTING FIXTURES |
| | WHICH ARE NOT IN THE INPUT DATA REPORT. THE INPUT DATA |
| | REPORT WILL BE NOTED AS IDR FOR THE REMAINDER OF THIS |
| | COMMENT. |
| | PLEASE SEE THE PLANS AS THE LIGHTING PERFORMANCE |
| | CALCULATIONS SHOWN DO NOT COORDINATE WITH THE SUBMITTED |
| | CALCULATIONS. THE LIGHTING PERFORMANCE CALCULATIONS ON |
| | PLANS DO NOT NEED TO BE THERE IF COMPLIANCE IS GOING TO |
| | BE SHOWN IN THE METHOD *B* CALCULATIONS. |
| | ** SOME EXAMPLES OF THESE ARE GIVEN BELOW. |
| | |
| | FOR EXAMPLE: |
| | PLANS SHOW A TOTAL OF 20 108W FIXTURES YET THE IDR ONLY |
| | CONTAINS 17 OF THESE. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE THE FIXTURE *J* AS SHOWN ON PLANS AND ON |
| | FIXTURE LEGEND IS A 26WATT FIXTURE. PLANS SHOW 4 OF |
| | THESE AND YET THE IDR DO NOT SHOW ANY 26WATT FIXTURES. |
| | |
| | FOR EXAMPLE: |
| | PLEASE SEE PLANS INDICATE *L* FIXTURES WHICH ARE SHOWN |
| | AS 50W FIXTURES YET THE IDR DOES NOT CONTAIN ANY 50WATT |
| | FIXTURES. |
| | |
| | ** PLEASE COORDINATE ALL OF THE ABOVE. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |