Plan Review Notes
Plan Review Notes For Permit 08030072
Permit Number 08030072
Review Stop M
Sequence Number 2
Notes
Date Text
2008-06-02 15:39:41REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1 THROUGH 5: OK
  
 6. RTU ATTACHMENT DETAIL AND CALCULATIONS HAVE BEEN
 RECEIVED AND WILL BE REVIEWED BY THE BUILDING PLAN
 REVIEWER. HOWEVER, NO INFORMATION WAS PROVIDED
 REGARDING THE ROOFTOP APPLIANCES THEMSELVES. PROVIDE
 DOCUMENTATION FROM THE APPLIANCE MANUFACTURER SHOWING
 RTUS THEMSELVES ARE DESIGNED TO RESIST ANTICIPATED WIND
 PRESSURES IN ACCORDANCE WITH FBCM 301.13.
  
 7 THROUGH 9: OK
  
 10. NOTE # 3 ON RTU SCHEDULE CALLS FOR MANUAL DAMPER ON
 OUTSIDE AIR INTAKE. FBC 13-409.1.ABC.3.3 CALLS FOR
 MOTORIZED DAMPERS FOR OUTSIDE AIR INTAKES IN EXCESS OF
 300 CFM. THESE DAMPERS SHALL AUTOMATICALLY SHUT WHEN
 THE SYSTEMS OR SPACES SERVED ARE NOT IN USE IN
 ACCORDANCE WITH THIS SECTION. A MANUAL DAMPER MAY BE
 USED FOR BALANCING BUT THE MOTORIZED DAMPER IS REQUIRED
 FOR COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION
 CODE.
  
 11. OK
  
 12. A) THE WRITTEN RESPONSE FROM THE ENGINEER STATES,
 ?ENERGY CALCS AND LOAD CALCS HAVE BEEN PROVIDED.? NO
 ENERGY CALCULATIONS COULD BE FOUND WITH THIS SUBMITTAL.
 PROVIDE ENERGY CALCULATIONS AS PREVIOUSLY REQUESTED.
 NOTE: WHEN PROVIDING ENERGY CALCULATION, BE SURE TO
 PROVIDE METHOD B OR C COMPLIANCE FORMS AS THIS IS
 NEITHER NEW CONSTRUCTION NOR AN ADDITION. RENOVATED
 COMMERCIAL BUILDINGS SHALL, WHEN APPLICABLE (SEE
 SECTION 202 OF CHAPTER 13 FOR A DEFINITION OF A
 RENOVATION), COMPLY WITH THE PRESCRIPTIVE REQUIREMENTS
 CONTAINED IN FORM 400C OR WITH METHOD B OF SUBCHAPTER
 13-4 FOR INSULATION, HVAC SYSTEMS, LIGHTING, WATER
 HEATING SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS BEING
 RETROFITTED OR REPLACED.
  
 B) THE SYSTEM SIZING SUMMARY PROVIDED INDICATES A
 DESIGN OUTDOOR AIRFLOW OF 500 CFM PER UNIT. THIS DOES
 NOT CORRESPOND WITH THE OUTSIDE AIR CALCULATIONS SHOWN
 ON PG M-1. PROVIDE A SUMMARY USING VALUES WHICH
 CORRESPOND WITH THE CONDITIONS SHOWN ON PLANS.
  