| 2008-06-02 15:39:41 | REVIEW #: 2ND |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | 1 THROUGH 5: OK |
| | |
| | 6. RTU ATTACHMENT DETAIL AND CALCULATIONS HAVE BEEN |
| | RECEIVED AND WILL BE REVIEWED BY THE BUILDING PLAN |
| | REVIEWER. HOWEVER, NO INFORMATION WAS PROVIDED |
| | REGARDING THE ROOFTOP APPLIANCES THEMSELVES. PROVIDE |
| | DOCUMENTATION FROM THE APPLIANCE MANUFACTURER SHOWING |
| | RTUS THEMSELVES ARE DESIGNED TO RESIST ANTICIPATED WIND |
| | PRESSURES IN ACCORDANCE WITH FBCM 301.13. |
| | |
| | 7 THROUGH 9: OK |
| | |
| | 10. NOTE # 3 ON RTU SCHEDULE CALLS FOR MANUAL DAMPER ON |
| | OUTSIDE AIR INTAKE. FBC 13-409.1.ABC.3.3 CALLS FOR |
| | MOTORIZED DAMPERS FOR OUTSIDE AIR INTAKES IN EXCESS OF |
| | 300 CFM. THESE DAMPERS SHALL AUTOMATICALLY SHUT WHEN |
| | THE SYSTEMS OR SPACES SERVED ARE NOT IN USE IN |
| | ACCORDANCE WITH THIS SECTION. A MANUAL DAMPER MAY BE |
| | USED FOR BALANCING BUT THE MOTORIZED DAMPER IS REQUIRED |
| | FOR COMPLIANCE WITH THE FLORIDA ENERGY CONSERVATION |
| | CODE. |
| | |
| | 11. OK |
| | |
| | 12. A) THE WRITTEN RESPONSE FROM THE ENGINEER STATES, |
| | ?ENERGY CALCS AND LOAD CALCS HAVE BEEN PROVIDED.? NO |
| | ENERGY CALCULATIONS COULD BE FOUND WITH THIS SUBMITTAL. |
| | PROVIDE ENERGY CALCULATIONS AS PREVIOUSLY REQUESTED. |
| | NOTE: WHEN PROVIDING ENERGY CALCULATION, BE SURE TO |
| | PROVIDE METHOD B OR C COMPLIANCE FORMS AS THIS IS |
| | NEITHER NEW CONSTRUCTION NOR AN ADDITION. RENOVATED |
| | COMMERCIAL BUILDINGS SHALL, WHEN APPLICABLE (SEE |
| | SECTION 202 OF CHAPTER 13 FOR A DEFINITION OF A |
| | RENOVATION), COMPLY WITH THE PRESCRIPTIVE REQUIREMENTS |
| | CONTAINED IN FORM 400C OR WITH METHOD B OF SUBCHAPTER |
| | 13-4 FOR INSULATION, HVAC SYSTEMS, LIGHTING, WATER |
| | HEATING SYSTEMS AND EXTERIOR ENVELOPE COMPONENTS BEING |
| | RETROFITTED OR REPLACED. |
| | |
| | B) THE SYSTEM SIZING SUMMARY PROVIDED INDICATES A |
| | DESIGN OUTDOOR AIRFLOW OF 500 CFM PER UNIT. THIS DOES |
| | NOT CORRESPOND WITH THE OUTSIDE AIR CALCULATIONS SHOWN |
| | ON PG M-1. PROVIDE A SUMMARY USING VALUES WHICH |
| | CORRESPOND WITH THE CONDITIONS SHOWN ON PLANS. |
| | |