2009-03-04 14:24:01DENIED
 REFERENCE:
 FBC-2004 FUEL GAS
  
 1. SHT P-3 GAS PIPING DIAGRAM. PLEASE SHOW THE REQUIRED
 DRIP/SEDIMENT TRAP. SECTIONS 408.2 & 408.4.
  
 2. SUBMIT MANUFACTURE SHEETS FOR THE TANKLESS WATER
 HEATER TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54 &
 FBC-2004 FUEL GAS SECTION 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.