Plan Review Notes
Plan Review Notes For Permit 08030072
Permit Number 08030072
Review Stop E
Sequence Number 2
Notes
Date Text
2008-06-11 09:06:02** DENIED 2ND REVIEW **
  
 ** THIS PROJECT IS STILL ONLY SUBMITTED FOR *PLAN
 REVIEW* ONLY AND IS NOT SUBMITTED UNDER PERMIT
 APPLICATION.
  
 ** PLEASE SEE THERE ARE STILL SOME ITEMS FROM PREVIOUS
 REVIEW WHICH ARE IN NEED OF ADDRESSING. THERE ARE ALSO
 NEW COMMENTS BASED ON REVISED PLANS/RISER NOW SHOWN AND
 INFORMATION WHICH WAS NOT ON PREVIOUS PLANS.
  
 ** IT IS IMPORTANT TO UNDERSTAND AS THERE ARE ITEMS NOT
 IN DESIGN YET AT THIS TIME OR SHOWN ON PLANS, NEW
 COMMENTS MAY BE GENERATE WHICH CAN NOT POSSIBLY BE MADE
 AT THIS TIME. REVIEWS ARE DONE BASED ON PLANS
 SUBMITTED.
  
 1) NOTE: PLEASE SEE COMPLIANCE FOR LIGHTING CONTROLS
 STILL NEED TO BE ADDRESSED. PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3.
 SECTION 13-415.1.ABC.1.4 WILL APPLY FOR ANY OUTSIDE
 LIGHTING.
 PLEASE SEE SECTIONS OF CODES NOTED ABOVE WITH RESPECT
 TO INTERIOR LIGHTING. THE PLANS CAME BACK WITH A
 LIGHTING CONTROL PANEL/TIME CLOCK AND THE RESPONSE
 MENTIONS MANUAL CONTROLS ARE SHOWN BY SWITCHES IN
 SEPARATE SPACES. THE SEPARATE SPACE CONTROLS ARE
 REQUIRED TO OVER RIDE ANY TIME OF DAY SCHEDULING AND
 ARE ALSO LIMITED IN THE TIME OF THE OVER RIDES.
 STANDARD SWITCHES SHOWN ON PLANS DO NOT COMPLY WITH THE
 FLORIDA BUILDING CODE FOR ENERGY CODE COMPLIANCE. AS
 SHOWN ON PLANS, IF AN OCCUPANT TURNS A LIGHT SWITCH ON
 IN ANY ROOM IN *OUT OF BUSINESS HOURS* THE LIGHTING
 WOULD REMAIN ON INDEFINITELY. AUTOMATED CONTROLS FOR
 *ALL* LIGHTING WITHIN THIS BUILDING IS REQUIRED
 INCLUDING THAT OF SEPARATE SPACES TO OVER-RIDE TIME OF
 DAY SCHEDULING AS NOTED.
 AS NOT SYSTEM, DEVICES ETC WERE SHOWN IN DESIGN A FULL
 REVIEW OF SEVERAL ITEMS COULD NOT BE DONE AT THIS
 TIME.
 ** AS NOTED ABOVE, OUTSIDE LIGHTING IN PARKING LOTS,
 DECORATIVE ETC OF ANY KIND WHICH WILL BE FED ON THIS
 PROPERTY SHALL HAVE LIGHTING CONTROLS.
 PLEASE KNOW THERE ARE MINIMUM LIGHTING REQUIRED IN
 PARKING LOTS UNDER ZONING REQUIREMENTS IN DEFINED AREAS
 OF THE CITY OF WEST PALM BEACH.
 IF THERE IS EXISTING LIGHTING IN PARKING LOT AT THIS
 TIME WHICH ARE FED FROM PANELS, PLEASE BE SURE TO SEE
 SECTION AS NOTED ABOVE FOR OUTDOOR LIGHTING.
 ** AS NOTED ON PREVIOUS REVIEW **
  
 2) NOTE: PLEASE SEE REQUIREMENTS FOR LIGHTING
 PERFORMANCE DOES NOT MEET FLORIDA BUILDING CODE FOR
 ENERGY EFFICIENCIES. PLEASE SEE 13-415.2,
 13-415.2.ABC.1.1, .1.2, .1.3.
 THE RESPONSE MENTIONS TO SEE LIGHTING CALCULATIONS
 SHOWN ON PLANS. THE REVIEW OF THESE CALCULATIONS SHOWS
 THE MINIMUM DESIGN EXCEEDING THE ALLOWANCES BY THE
 CODE. THERE ARE SEVERAL ITEMS WHICH WILL BE NOTED
 BELOW.
 **AS NOTED ON PREVIOUS REVIEW**
  
 A) MAY NOT USE RETAIL AS THE OCCUPANCY AS STATED IN
 FLORIDA BUILDING CODE AND NFPA-101 STATES THIS IS
 BUSINESS OCCUPANCY. THEREFORE THE ALLOWANCES SHOWN IN
 TABLES MUST ONLY USE OFFICE.
 THIS APPLIES TO MOST AREAS ON PLANS WHICH SHOWS *SALES
 AREAS* AS THE ALLOWED USE. ONE EXAMPLE OF AN AREA WHICH
 CAN NOT BE *SALES AREA* IS THE *CHANGING ROOM*. THIS IS
 ONLY ONE EXAMPLES AS MOST OF THE AREAS NOTED AS SALES
 AREAS ARE JUST NOT SALES AREAS. THE CLOSET AS SHOWN IS
 NOT CONSIDERED *ACTIVE STORAGE* BASED ON USE SHOWN ON
 PLANS.
 THE CODE IS CLEAR FOR USE AND OCCUPANCIES. PLEASE KNOW
 AS INFORMATIONAL USE, MAY NOT USE 3.9 WATTS PER SQ FT
 AS FIGURED IN TABLE. THIS OCCUPANCY AND USE IS NOT
 INCLUDED.
 THESE ARE ONLY A COUPLE OF EXAMPLES.
  
 B) THE ALLOWANCES SHOWN ON PLANS FOR DECORATIVE
 LIGHTING ALSO EXCEED TABLES AND EXCEPTIONS TO TABLES.
 THE ALLOWANCE FOR DECORATIVE LIGHTING ABOVE THE GENERAL
 LIGHTING IS ONLY 1W PER SQ/FT. THE WATTAGE SHOWN
 EXCEEDS THIS LEVEL SUBSTANTIALLY.
  
 C) PLEASE SEE THE ALLOWANCES FOR DECORATIVE LIGHTS ETC
 MAY ONLY BE USE WHEN ACTUALLY INSTALLING THESE TYPES OF
 LIGHTS. CALCULATIONS SUBMITTED SHOW AN ALLOWANCE BEING
 ASSUMED WHEN NO DECORATIVE LIGHTING IS BEING
 INSTALLED.
  
 D) PLEASE SUBMIT ENERGY CALCULATIONS. AS NOTED IN
 MECHANICAL REVIEW NONE WERE LOCATED IN PLANS ETC
 SUBMITTED. PLEASE KNOW THIS OFFICE GIVES NOTICE TO
 PLEASE BE SURE ALL INFORMATION SHOWN ON PLANS IS
 SUBMITTED AND SHOWN ON THE SUBMITTED ENERGY
 CALCULATIONS. PLEASE BE SURE ALL INFORMATION ON THE
 INPUT DATA REPORT WHEN SUBMITTED COORDINATES WITH THE
 SUBMITTED PLANS.
 13-400.3.B, 13-400.3.C, 13-101.1.3
  
 ** PLEASE GO OVER ACTUAL CODE PERMITTED ALLOWANCES.
 PLEASE SEE SOME OF THE EXAMPLES ABOVE FOR NON-CODE
 COMPLIANCE IS GIVEN AS A BENEFIT AND IS NOT ALL ITEMS
 IN LIGHTING PERFORMANCE CALCULATIONS SUBMITTED WHICH DO
 NOT COMPLY.
  
 3) NOTE: PLEASE SEE RISER DOES NOT SHOW ANY METERING
 DEVICE ON THE MAIN 1 OF 2 WHICH APPEARS TO BE FOR THE
 SECOND TENANT. PLEASE SEE FPL MINIMUM SERVICE
 REQUIREMENTS WHICH AT THIS TIME HAVE NOT BEEN MET BY
 THE INFORMATION SHOWN ON RISER.
  
 4) NOTE: PLEASE SEE 250.6, 250.24. THE RISER SHOWS
 *EQUIPMENT GROUNDING CONDUCTORS* BEING INSTALLED BEFORE
 THE FIRST MEANS OF DISCONNECT(S) WHICH IS NOT
 PERMITTED. AS SHOWN THESE WOULD PARALLEL THE NEUTRAL
 CONDUCTORS THUS CREATING OBJECTIONABLE CURRENTS. PLEASE
 REMOVE ALL EQUIPMENT GROUNDING CONDUCTORS BEFORE THE
 FIRST MEANS OF DISCONNECTS.
  
 5) NOTE: PLEASE SEE RISER NOTE #9 WHICH CALLS FOR
 INTERRUPTION OF *FEEDERS* TO GO TO MAIN ONE OF TWO.
 THESE ARE NOT FEEDERS.
 PLEASE SEE NEC FOR DEFINITIONS IN ART 100, 230, 215,
 ETC
  
 6) NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND PLACE
 NOTES ON PLANS ACCORDINGLY. THERE WAS NO RESPONSE IN
 THE RESPONSE LETTER SUBMITTED. THIS WAS NOTED ON
 PREVIOUS REVIEW.
  
 7) NOTE: PLEASE PROVIDE INFORMATION AND SHOW EGRESS
 LIGHTING ON EXIT ACCESS CORRIDOR. IS THE LIGHTING GOING
 TO BE NEW OR EXISTING? PLEASE SHOW THE MINIMUM LIGHTING
 AND EXIT LIGHTING PER NFPA-101 7.8, 7.9.
 THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY ANY
 OTHER TRADE REVIEW.
  
 8) NOTE: PLEASE CLARIFY THE REAR HALLWAY. SOME SHEETS
 SHOW THE PREVIOUS EGRESS DOOR FROM OTHER TENANT SPACE
 BEING NOTED AS SEALED UP YET SOME SHEETS INDICATE THIS
 DOOR WILL BE *EXISTING TO REMAIN*.
 HOW WILL EGRESS FOR ADJACENT TENANT TAKE PLACE?
 IS THIS HALLWAY A COMMON AREA?
 THE NOTES ON PLANS DO NOT IDENTIFY THIS HALL WAY AS ANY
 ONE SPACE FOR EITHER TENANTS.
 SHEET A1 STATES THE ELECTRICAL PANELS SHOWN WILL
 REMAIN. IF THESE PANELS ARE FOR OTHER TENANT THEN THEY
 NEED TO BE RELOCATED INTO THE OTHER TENANT SPACE UNLESS
 THIS IS A COMMON AREA.
 IF THIS IS A COMMON AREA AND NOT PART OF EITHER TENANT
 THEN LIGHTING ETC WILL BE REQUIRED TO BE FED FROM A
 *HOUSE PANEL*.
  
 *** THESE ITEMS MAY BE BUILDING AND FIRE REVIEW RELATED
 HOWEVER MUST COMPLY WITH THE MINIMUM REQUIREMENTS OF
 THE FLORIDA BUILDING CODE AND ALL OTHER ADOPTED CODES,
 LAWS AND ORDINANCES.
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 9) NOTE: PLEASE SEE 408.4, ALL CIRCUITING ON PLANS AND
 PANEL SCHEDULE SHALL BE SPECIFIC. LISTING *LIGHTING* AS
 A DESCRIPTION IS NOT SPECIFIC TO ROOMS OR AREAS.
  
 10) NOTE: PLEASE KNOW THE APPLIED VALUE FOR SCOPE OF
 WORK IS YET TO BE REVIEWED. THIS DOES AFFECT SECTIONS
 OF THE CODE(S) WHICH CAN NOT BE REVIEWED AT THIS TIME.
 FBC 108.3.
  
 11) NOTE: PLEASE SHOW AND IDENTIFY ALL PANELS ON RISER
 AND ON PLANS. AS NOTED IN NOTED #8 ABOVE, AREAS IN
 WHICH THESE PANELS ARE LOCATED HAVE NOT BEEN DETERMINED
 TO COMPLY WITH SECTIONS OF THE CODE(S).
 240.24, 110.26 ETC.
  
 12) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES AS THE
 ADDRESS ON TITLE BLOCKS CALL FOR 2401 ON SOME SHEETS
 AND 2409 ON OTHERS.FAC 61G1-16.004, 61G15-23.002, FBC
 106.5
  
 *** PLEASE KNOW THERE MAY VERY WELL BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH CAN NOT BE MADE AT THIS TIME DUE
 TO INFORMATION ETC NOT YET IN DESIGN OR ON PLANS.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717