| Plan Review Notes For Permit 08030072 |
| Permit Number |
08030072 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-04-11 08:46:22 | DENIED; | | | 1. ADD A DEMO NOTE; NO DEAD ENDS PERMITED IN THE | | | DRAINAGE SYSTEM LONGER THAN 2 FEET, INSPECTION | | | REQUIRED. | | | 2. BOTH BATHROOMS ARE REQUIRED TO MEET ACCESSIBILITY | | | REQUIREMENTS. SEE FBC-BUILDING CHAPTER 11, SECTION | | | 11-4.1.2(6). MINUMUM WIDTH WOULD BE 5' 3", 18" TO | | | CENTER OF W/C, 30" FROM CENTER OF W/C TO CENTER OF | | | LAV., AND 15" FROM CENTER OF LAV TO WALL. | | | 3. STAFF LOUNGE SINKS TO MEET ACCESSIBILITY | | | REQUIREMENTS, SEE SECTIONS 11-4.24.1 THRU 11-4.24.7, | | | SHOW DETAIL DRAWING WITH ALL REQUIRED DIMENSIONS AND | | | REQUIREMENTS. | | | 4. SHOW DETAIL OF DRINKING FOUNTAIN WITH ALL REQUIRED | | | MEASUREMENTS, TO MEET CODE SECTIONS 11-4.15.1 THRU | | | 11-4.15.5. | | | 5. SHOW CLEAR FLOOR SPACE AT BREAK SINK ON FLOOR PLAN | | | PAGE A-4. | | | 6. SHOW DETAIL OF ELECTRIC WATER HEATER, HOW HUNG, | | | EXPANSION CONTROL, SECTION 607.3, HEATER PAN AND DRAIN, | | | SECTION 504.7.1 AND 504.7.2. | | | 7. PLEASE REMOVE ALL AIR CHAMBER SYMBOLS FROM WATER | | | RISER DIAGRAM, AIR CHAMBERS ARE NOT RECOGNIZED IN THE | | | FBC-PLUMBING, SHOCK ARRESTORS ONLY AS REQUIRED BY | | | SECTION 604.9. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|