Plan Review Notes
Plan Review Notes For Permit 08030072
Permit Number 08030072
Review Stop P
Sequence Number 1
Notes
Date Text
2008-04-11 08:46:22DENIED;
 1. ADD A DEMO NOTE; NO DEAD ENDS PERMITED IN THE
 DRAINAGE SYSTEM LONGER THAN 2 FEET, INSPECTION
 REQUIRED.
 2. BOTH BATHROOMS ARE REQUIRED TO MEET ACCESSIBILITY
 REQUIREMENTS. SEE FBC-BUILDING CHAPTER 11, SECTION
 11-4.1.2(6). MINUMUM WIDTH WOULD BE 5' 3", 18" TO
 CENTER OF W/C, 30" FROM CENTER OF W/C TO CENTER OF
 LAV., AND 15" FROM CENTER OF LAV TO WALL.
 3. STAFF LOUNGE SINKS TO MEET ACCESSIBILITY
 REQUIREMENTS, SEE SECTIONS 11-4.24.1 THRU 11-4.24.7,
 SHOW DETAIL DRAWING WITH ALL REQUIRED DIMENSIONS AND
 REQUIREMENTS.
 4. SHOW DETAIL OF DRINKING FOUNTAIN WITH ALL REQUIRED
 MEASUREMENTS, TO MEET CODE SECTIONS 11-4.15.1 THRU
 11-4.15.5.
 5. SHOW CLEAR FLOOR SPACE AT BREAK SINK ON FLOOR PLAN
 PAGE A-4.
 6. SHOW DETAIL OF ELECTRIC WATER HEATER, HOW HUNG,
 EXPANSION CONTROL, SECTION 607.3, HEATER PAN AND DRAIN,
 SECTION 504.7.1 AND 504.7.2.
 7. PLEASE REMOVE ALL AIR CHAMBER SYMBOLS FROM WATER
 RISER DIAGRAM, AIR CHAMBERS ARE NOT RECOGNIZED IN THE
 FBC-PLUMBING, SHOCK ARRESTORS ONLY AS REQUIRED BY
 SECTION 604.9.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695