| 2008-03-26 14:17:22 | REVIEW #: 1ST **PLAN CHECK ONLY** |
| | ACTION: DENOED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. M-1: SIZE OF RETURN GRILLS IN WAXING ROOM AND AT |
| | REAR ENTRANCE ABOVE WATER FOUNTAINS ARE MISSING. |
| | CORRECT AND RESUBMIT. FBCM 603.1 |
| | |
| | 2. M-1: SIZE OF TRUNK LINE FEEDING STAFF LOUNGE AND |
| | OFFICE IS MISSING. PLEASE CORRECT AND RESUBMIT. FBCM |
| | 603.1 |
| | |
| | 3. M-1: A SPACE-BY-SPACE ANALYSIS OF THE VENTILATION |
| | REQUIREMENTS OF THE PROPOSED SPACES INDICATES THAT THE |
| | OUTSIDE AIR PROVIDED IS INADEQUATE BASED ON FBCM TABLE |
| | 403.3. WITH EACH SPACE ADDED UP THE APPROXIMATE TOTAL |
| | IS 1675 CFM. THE TOTAL MAY ACTUALLY BE HIGHER BASED ON |
| | THE FACT THAT A COMMON VENTILATION SYSTEM IS BEING |
| | USED. PLEASE PROVIDE OUTSIDE AIR CALCULATIONS BASED ON |
| | THE OCCUPANT LOAD AS LISTED IN THE SPECIALTY SHOPS- |
| | BEAUTY OCCUPANCY IN TABLE 403.3. THIS WOULD REQUIRE AN |
| | OCCUPANT LOAD OF 25 PEOPLE PER 1000SF OF FLOOR AREA |
| | (FOR THE ENTIRE FLOOR AREA) AND A VENTILATION TARE OF |
| | 25 CFM PER PERSON. |
| | |
| | 4. M-1: THE NAIL SALON PORTION OF THE SPACE IS SUBJECT |
| | TO FOOTNOTE B OF TABLE 403.3, WHICH PROHIBITS AIR |
| | SUPPLIED TO THIS SPACE FROM BEING RECIRCULATED IN |
| | ACCORDANCE WITH FBCM 403.2.1(3). HOW WILL AIR FROM THIS |
| | SPACE BE PREVENTED FROM RECIRCULATING WITH |
| | PARTIAL-HEIGHT PARTITIONS AND A COMMON RETURN? ALSO, |
| | ACCORDING TO THE FLOOR PLAN, 730 CFM OF SUPPLY IS |
| | PROVIDED IN THIS LOCATION WITH ONLY 400 CFM OF EXHAUST. |
| | ALL AIR SUPPLIED TO THIS SPACE SHALL BE EXHAUSTED TO |
| | PREVENT RECIRCULATION IN ACCORDANCE WITH FBCM |
| | 403.2.1(3). |
| | |
| | 5. M-1: FLOOR PLAN SHOWS DUCT SMOKE DETECTORS IN SUPPLY |
| | RISERS ABOVE THE STAFF LOUNGE AND PROCESSING ROOMS. |
| | THESE ROOMS SHAVE HARD GYPSUM PANEL CEILINGS AS SHOWN |
| | ON PG A-4. ACCESS SHALL BE PROVIDED TO SMOKE DETECTORS |
| | FOR INSPECTION AND MAINTENANCE IN ACCORDANCE WITH FBCM |
| | 606.3. |
| | |
| | 6. M-2: MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS |
| | THAT ARE EXPOSED TO WIND SHALL BE DESIGNED AND |
| | INSTALLED TO RESIST THE WIND PRESSURES ON THE EQUIPMENT |
| | AND THE SUPPORTS AS DETERMINED IN ACCORDANCE WITH FBCB |
| | CHAPTER 16 PER FBCM 301.13. PROVIDE WIND LOAD |
| | CALCULATIONS FOR APPLIANCE ATTACHMENT TO STRUCTURE TO |
| | SUPPORT THE ATTACHMENT DETAIL FOR BUILDING PLAN REVIEW. |
| | ALSO, PROVIDE DATA FROM THE MANUFACTURER OF THE OUTDOOR |
| | APPLIANCES (RTU?S) SHOWING THEY HAVE BEEN DESIGNED AND |
| | TESTED TO WITHSTAND ANTICIPATED WIND LOADS IN |
| | ACCORDANCE WITH FBCM 301.13 AND FBCB SECTION 1609. |
| | |
| | 7. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL. |
| | CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL |
| | BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED |
| | PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO |
| | A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A |
| | NUISANCE IN ACCORDANCE WITH FBCM 307.2.1 |
| | |
| | 8. PROVIDE AUXILIARY DRAIN PROTECTION IN ACCORDANCE |
| | WITH FBCM 307.2.3. A WATER LEVEL DETECTION DEVICE (SUCH |
| | AS A FLOAT SWITCH) INSTALLED INTERNALLY ON THE PRIMARY |
| | DRAIN PAN WILL MEET THIS REQUIREMENT. |
| | |
| | 9. PG M-2: GENERAL NOTE #17, PLEASE REFERENCE THE |
| | CORRECT CODE. THIS PROJECT IS BEING REVIEWED UNDER THE |
| | 2004 FLORIDA BUILDING CODE W/ 2007 AMENDMENTS. |
| | |
| | 10. PROVIDE SHUTOFF DAMPER CONTROLS ON OUTSIDE AIR AND |
| | EXHAUST IN ACCORDANCE WITH FBCB 13-409.1.ABC.3.3. |
| | |
| | 11. PROVIDE AN AIR BALANCE SCHEDULE TO SHOW THE |
| | MECHANICAL SYSTEMS ARE DESIGNED TO ASSURE THAT |
| | BUILDINGS ARE PRESSURIZED WITH RESPECT TO OUTDOORS IN |
| | ACCORDANCE WITH FBCB 13-409.1.ABC.2. |
| | |
| | 12. ENERGY CALCULATIONS WERE NOT PROVIDED. RENOVATED |
| | COMMERCIAL BUILDINGS SHALL, WHEN APPLICABLE (SEE |
| | SECTION 202 OF FBCB CHAPTER 13), COMPLY WITH THE |
| | PRESCRIPTIVE REQUIREMENTS CONTAINED IN FORM 400C OR |
| | WITH METHOD B OF SUBCHAPTER 13-4 FOR INSULATION, HVAC |
| | SYSTEMS, LIGHTING, WATER HEATING SYSTEMS AND EXTERIOR |
| | ENVELOPE COMPONENTS BEING RETROFITTED OR REPLACED IN |
| | ACCORDANCE WITH FBCB 13-101.1.3. PROVIDE ENERGY |
| | CALCULATIONS TO DEMONSTRATE COMPLIANCE. SYSTEM SIZING |
| | MAY NEED TO BE REDONE BASED ON ENERGY CALCULATIONS AND |
| | RECALCULATED OUTSIDE AIR RATES. |
| | |