| 2008-03-17 17:09:05 | ** DENIEDREVIEW** |
| | |
| | 1) NOTE: PLEASE SEE THAT THE PLANS WERE ONLY SUBMITTED |
| | FOR PLAN REVIEW AND HAVE NOT BEEN SUBMITTED FOR |
| | PERMIT. |
| | ONCE ALL COMMENTS ARE ADDRESSED AND PERMIT APPLICATION |
| | HAS NOT BEEN MADE REVIEW WILL STILL REMAIN IN FAILED |
| | STATUS UNTIL PERMIT HAS BEEN APPLIED FOR. |
| | REVIEW OF LICENSING ETC WILL BE DONE AT PERMIT |
| | APPLICATION BEFORE PERMIT ISSUANCE. |
| | |
| | 2) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED |
| | ON ELECTRICAL PLANS AS WELL AS ARCHITECTURAL. |
| | 2004 FBC W2007 REVISIONS |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 (IF APPLICABLE) |
| | |
| | 3) NOTE: PLEASE SEE THE PLANS AND RISER SEEMS TO SHOW A |
| | MAIN TWO OF TWO HOWEVER DOES NOT SHOW HOW THIS MAIN IS |
| | CONNECTED INTO THE NEW SERVICE. |
| | AT THIS TIME IT APPEARS THERE IS A NEW SERVICE BEING |
| | PROPOSED AND NOT ENOUGH INFORMATION TO GRANT A SEPARATE |
| | SERVICE PER 230.2 |
| | 240.4, 310.16, ETC |
| | FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 4) NOTE: PLEASE SEE MISSING LIGHTING PERFORMANCE |
| | CALCULATIONS AND ENERGY CALCULATIONS PER 13-415.2, |
| | 13-400.3.B, 13-400.3.C ETC. |
| | PLEASE SEE BE SURE TO SEE 13-415.2.ABC.1.1, .1.2 AND |
| | .1.3 FOR LIGHTING INPUTS. |
| | PLEASE BE SURE ALL LIGHTING ON PLANS COORDINATES WITH |
| | CALCULATIONS WHEN SUBMITTED. |
| | |
| | 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND |
| | .1.4 FOR MISSING LIGHTING CONTROLS REQUIRED. |
| | PLEASE SEE THE PLANS DO SHOW SOME KIND OF LIGHTING |
| | PANEL, HOWEVER PLANS DO NOT SHOW ANY OVER RIDES, OVER |
| | RIDE LOCATIONS, SEPARATE SPACES CONTROLS, SCHEDULING, |
| | MAXIMUM TIMES ON DEVICES. ETC. |
| | PLEASE INDICATE IF TIME CLOCK FOR ANY OUTSIDE LIGHTING |
| | IS ASTRONOMICAL WITH MINIMUM 10HR BATTERY BACK UP. |
| | ** AS NO SYSTEM, DEVICES ETC WERE SUBMITTED FOR |
| | COMPLETE SYSTEM, A FULL REVIEW COULD NOT BE DONE AT |
| | THIS TIME. |
| | |
| | 6) NOTE: PLEASE VERIFY NO OUTSIDE LIGHTS, PARKING ETC |
| | ARE SHOWN. |
| | FBC 106.1.2 |
| | |
| | 7) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH |
| | CIRCUITS IN PANEL SCHEDULE. PLEASE SEE 408.4 WHICH |
| | REQUIRES ALL CIRCUITS TO BE NOTED SPECIFIC TO EACH |
| | LOCATION IN WHICH THEY ARE FEEDING. |
| | FOR EXAMPLE: PLEASE SEE PANEL *B* WHICH INDICATES TWO |
| | DEDICATED SIGN CIRCUITS AS REQUIRED PER 600.5 HOWEVER |
| | PLEASE SEE PLANS AS BOTH SIGN CIRCUITS ARE NOTED ON THE |
| | SAME CIRCUIT WHICH IS NOT PERMITTED. |
| | |
| | 8) NOTE: PLEASE SHOW HOW LOADS FOR SHOW WINDOWS WERE |
| | FIGURED INTO LOAD CALCULATIONS. |
| | 220.43A |
| | |
| | 9) NOTE: PLEASE SEE 422.13 AS THE WATER HEATER IS |
| | CONSIDERED A CONTINUOUS LOAD AND LOAD SHOULD BE NOTED |
| | ACCORDINGLY. |
| | |
| | 10) NOTE: PLEASE SEE THE MDP INDICATE A TWO POLE SINGLE |
| | PHASE FEED TO PANEL *B* YET BY THE CIRCUITING SHOWN ON |
| | MDP, THIS WOULD PLACE A HIGH-LEG ON PANEL *B* FEEDERS |
| | WHICH CONTAIN SINGLE POLE 120V CIRCUITS. |
| | PLEASE ADJUST. |
| | 110.3, 90.7 |
| | FBC 106.1.2 |
| | |
| | 11) NOTE: PLEASE SUBMIT AIC RATINGS FOR ANY NEW SERVICE |
| | EQUIPMENT. 110.9 |
| | PLEASE BE AWARE OF NOTE ABOVE WITH RESPECT TO SERVICE |
| | PERMITTED AND ADJUSTMENTS NEEDED BASED ON SERVICE AS |
| | SHOWN. |
| | |
| | 12) NOTE: PLEASE SEE 250.104 AS GAS METALLIC PIPES |
| | REQUIRE BONDING. |
| | |
| | 13) NOTE: PLEASE SEE ARCHITECTURAL TITLE BLOCKS ARE |
| | MISSING THE REQUIRED PRINTED NAME AND PRINTED LICENSE |
| | NUMBER OF SAID DESIGNER. |
| | FAC 61G1-16.004. |
| | |
| | 14)NOTE: PLEASE SEE POSSIBLE BUILDING REVIEW COMMENTS |
| | WITH RESPECT TO EGRESS DOOR SWINGING INTO WHAT APPEARS |
| | TO EXIT ACCESS CORRIDOR. |
| | THIS IS ONLY NOTED BY THIS REVIEW AND IS NOT PLAN |
| | REVIEW NOTE. |
| | |
| | 15) NOTE: PLEASE SEE 13-415.1.ABC.2.1 AND .2.2 FOR |
| | MISSING NOTES ON PLANS. |
| | |
| | 16) NOTE: PLEASE BE SURE ADDRESSING AS APPLIED AND |
| | STATED ON PLANS COORDINATES. THIS HAS BEEN ROUTED TO |
| | ADDRESSING REVIEWER . |
| | AS APPLIEDTHE ADDRESS IS 2401-2405 N DIXIE, HOWEVER |
| | BASED ON COMPUTER AND PCN USED THIS ADDRESS IS 2409 |
| | DIXIE HWY. |
| | PLEASE BE SURE ONCE ADDRESS IS CONFIRMED THE TITLE |
| | BLOCKS ARE CORRECTED TO SHOW APPLIED LOCATION WITH |
| | FINAL DETERMINED ADDRESS. |
| | FAC 61G1-16.004, 61G15-23.002 |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |