Plan Review Notes
Plan Review Notes For Permit 08030072
Permit Number 08030072
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-17 17:09:05** DENIEDREVIEW**
  
 1) NOTE: PLEASE SEE THAT THE PLANS WERE ONLY SUBMITTED
 FOR PLAN REVIEW AND HAVE NOT BEEN SUBMITTED FOR
 PERMIT.
 ONCE ALL COMMENTS ARE ADDRESSED AND PERMIT APPLICATION
 HAS NOT BEEN MADE REVIEW WILL STILL REMAIN IN FAILED
 STATUS UNTIL PERMIT HAS BEEN APPLIED FOR.
 REVIEW OF LICENSING ETC WILL BE DONE AT PERMIT
 APPLICATION BEFORE PERMIT ISSUANCE.
  
 2) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON ELECTRICAL PLANS AS WELL AS ARCHITECTURAL.
 2004 FBC W2007 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (IF APPLICABLE)
  
 3) NOTE: PLEASE SEE THE PLANS AND RISER SEEMS TO SHOW A
 MAIN TWO OF TWO HOWEVER DOES NOT SHOW HOW THIS MAIN IS
 CONNECTED INTO THE NEW SERVICE.
 AT THIS TIME IT APPEARS THERE IS A NEW SERVICE BEING
 PROPOSED AND NOT ENOUGH INFORMATION TO GRANT A SEPARATE
 SERVICE PER 230.2
 240.4, 310.16, ETC
 FBC 106.3.5.1.2, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SEE MISSING LIGHTING PERFORMANCE
 CALCULATIONS AND ENERGY CALCULATIONS PER 13-415.2,
 13-400.3.B, 13-400.3.C ETC.
 PLEASE SEE BE SURE TO SEE 13-415.2.ABC.1.1, .1.2 AND
 .1.3 FOR LIGHTING INPUTS.
 PLEASE BE SURE ALL LIGHTING ON PLANS COORDINATES WITH
 CALCULATIONS WHEN SUBMITTED.
  
 5) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND
 .1.4 FOR MISSING LIGHTING CONTROLS REQUIRED.
 PLEASE SEE THE PLANS DO SHOW SOME KIND OF LIGHTING
 PANEL, HOWEVER PLANS DO NOT SHOW ANY OVER RIDES, OVER
 RIDE LOCATIONS, SEPARATE SPACES CONTROLS, SCHEDULING,
 MAXIMUM TIMES ON DEVICES. ETC.
 PLEASE INDICATE IF TIME CLOCK FOR ANY OUTSIDE LIGHTING
 IS ASTRONOMICAL WITH MINIMUM 10HR BATTERY BACK UP.
 ** AS NO SYSTEM, DEVICES ETC WERE SUBMITTED FOR
 COMPLETE SYSTEM, A FULL REVIEW COULD NOT BE DONE AT
 THIS TIME.
  
 6) NOTE: PLEASE VERIFY NO OUTSIDE LIGHTS, PARKING ETC
 ARE SHOWN.
 FBC 106.1.2
  
 7) NOTE: PLEASE CORRELATE ALL CIRCUITING ON PLANS WITH
 CIRCUITS IN PANEL SCHEDULE. PLEASE SEE 408.4 WHICH
 REQUIRES ALL CIRCUITS TO BE NOTED SPECIFIC TO EACH
 LOCATION IN WHICH THEY ARE FEEDING.
 FOR EXAMPLE: PLEASE SEE PANEL *B* WHICH INDICATES TWO
 DEDICATED SIGN CIRCUITS AS REQUIRED PER 600.5 HOWEVER
 PLEASE SEE PLANS AS BOTH SIGN CIRCUITS ARE NOTED ON THE
 SAME CIRCUIT WHICH IS NOT PERMITTED.
  
 8) NOTE: PLEASE SHOW HOW LOADS FOR SHOW WINDOWS WERE
 FIGURED INTO LOAD CALCULATIONS.
 220.43A
  
 9) NOTE: PLEASE SEE 422.13 AS THE WATER HEATER IS
 CONSIDERED A CONTINUOUS LOAD AND LOAD SHOULD BE NOTED
 ACCORDINGLY.
  
 10) NOTE: PLEASE SEE THE MDP INDICATE A TWO POLE SINGLE
 PHASE FEED TO PANEL *B* YET BY THE CIRCUITING SHOWN ON
 MDP, THIS WOULD PLACE A HIGH-LEG ON PANEL *B* FEEDERS
 WHICH CONTAIN SINGLE POLE 120V CIRCUITS.
 PLEASE ADJUST.
 110.3, 90.7
 FBC 106.1.2
  
 11) NOTE: PLEASE SUBMIT AIC RATINGS FOR ANY NEW SERVICE
 EQUIPMENT. 110.9
 PLEASE BE AWARE OF NOTE ABOVE WITH RESPECT TO SERVICE
 PERMITTED AND ADJUSTMENTS NEEDED BASED ON SERVICE AS
 SHOWN.
  
 12) NOTE: PLEASE SEE 250.104 AS GAS METALLIC PIPES
 REQUIRE BONDING.
  
 13) NOTE: PLEASE SEE ARCHITECTURAL TITLE BLOCKS ARE
 MISSING THE REQUIRED PRINTED NAME AND PRINTED LICENSE
 NUMBER OF SAID DESIGNER.
 FAC 61G1-16.004.
  
 14)NOTE: PLEASE SEE POSSIBLE BUILDING REVIEW COMMENTS
 WITH RESPECT TO EGRESS DOOR SWINGING INTO WHAT APPEARS
 TO EXIT ACCESS CORRIDOR.
 THIS IS ONLY NOTED BY THIS REVIEW AND IS NOT PLAN
 REVIEW NOTE.
  
 15) NOTE: PLEASE SEE 13-415.1.ABC.2.1 AND .2.2 FOR
 MISSING NOTES ON PLANS.
  
 16) NOTE: PLEASE BE SURE ADDRESSING AS APPLIED AND
 STATED ON PLANS COORDINATES. THIS HAS BEEN ROUTED TO
 ADDRESSING REVIEWER .
 AS APPLIEDTHE ADDRESS IS 2401-2405 N DIXIE, HOWEVER
 BASED ON COMPUTER AND PCN USED THIS ADDRESS IS 2409
 DIXIE HWY.
 PLEASE BE SURE ONCE ADDRESS IS CONFIRMED THE TITLE
 BLOCKS ARE CORRECTED TO SHOW APPLIED LOCATION WITH
 FINAL DETERMINED ADDRESS.
 FAC 61G1-16.004, 61G15-23.002
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]