Plan Review Notes
Plan Review Notes For Permit 08030072
Permit Number 08030072
Review Stop B
Sequence Number 1
Notes
Date Text
2008-04-10 15:34:51BUILDING PLAN REVIEW
 PERMIT: 08030072
 ADD: 2401-2405 N DIXIE HWY
 CONT:PLAN REVIEW
 TEL: (954)253-1716
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE
 INDICATE THE REVISION & REMOVE & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) INFORMATIONAL FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)INFORMATIONAL: PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE2007 SUPPLEMENTS.
  
 2)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 NOTE THE 2004 FBC W/ 2007 SUPPLEMENTS AND 2004
 EXISTING BUILDING CODE ARE BOTH TO BE USED IN DESIGN
 FOR REMODELING.
 PROVIDE WHAT LEVEL OF ALTERATION TO BE COMPLETED
 UNDER THIS PERMIT. EXXISTING BUILDING CODE 301.5. B)
 THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINEDIN CHAPTER 6,
 TABLE 601.
  
 3)PLEASE SEE THE EXIT CORRIDOR THAT IS SHARED BY BOTH
 TENANTS AND SECTION 605.1 IN THE 2004 EXISTING BUILDING
 CODE. THE DOORWAY FROM THE UNIT BEING REMODELED SWINGS
 INTO THE EXIT ACCESS CORRIDOR AND LEAVES LESS THAN THE
 REQUIRED 18".
 1008.1.8.8
 DURING ITS SWING, ANY DOOR IN A MEANS OF EGRESS SHALL
 LEAVE UNOBSTRUCTED AT LEAST ONE HALF OF THE REQUIRED
 WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY, OR LANDING,
 NOR PROJECT MORE THAN 7 INCHES (178 MM) INTO THE
 REQUIRED WIDTH OF AN AISLE, CORRIDOR, PASSAGEWAY OR
 LANDING, WHEN FULLY OPEN. DOORS SHALL NOT OPEN
 IMMEDIATELY ONTO A STAIR WITHOUT A LANDING. THE LANDING
 SHALL HAVE A WIDTH AT LEAST EQUAL TO THE WIDTH OF THE
 DOOR.
  
 4) A-4 ALSO INDICATES TWO DOORS B & C.
  
 4A) DOOR TYPE B IS A PAIR OF DOORS REQUIRING A CLEAR
 WIDTH OF 32". 1008.1.1 SIZE OF DOORS.
 THE MINIMUM WIDTH OF EACH DOOR OPENING SHALL BE
 SUFFICIENT FOR THE OCCUPANT LOAD THEREOF AND SHALL
 PROVIDE A CLEAR WIDTH OF NOT LESS THAN 32 INCHES (813
 MM). CLEAR OPENINGS OF DOORWAYS WITH SWINGING DOORS
 SHALL BE MEASURED BETWEEN THE FACE OF THE DOOR AND THE
 STOP, WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). WHERE
 THIS SECTION REQUIRES A MINIMUM CLEAR WIDTH OF 32
 INCHES (813 MM) AND A DOOR OPENING INCLUDES TWO DOOR
 LEAVES WITHOUT A MULLION, ONE LEAF SHALL PROVIDE A
 CLEAR OPENING WIDTH OF 32 INCHES (813 MM). THE MAXIMUM
 WIDTH OF A SWINGING DOOR LEAF SHALL BE 48 INCHES (1219
 MM) NOMINAL. MEANS OF EGRESS DOORS IN AN OCCUPANCY IN
 GROUP I-2 USED FOR THE MOVEMENT OF BEDS SHALL PROVIDE A
 CLEAR WIDTH NOT LESS THAN 41? INCHES (1054 MM). THE
 HEIGHT OF DOORS SHALL NOT BE LESS THAN 80 INCHES (2032
 MM). 11-4.13.4. DOUBLE LEAF DOORS.
  
 4B) DOOR C IN THE DEMO PLAN WAS AN OPENING OF 4'-0" YOU
 CAN'T REDUCE OPENINGS TO WHERE THEY ARE NOT CODE
 COMPLIANT. THE MINIMUMDOOR OPENING SIZE WOULD BE A
 2'-10" LEAVING A 32"
 OPENING. FLORIDA EXISTING BUILDING CODE 606.1 A
 BUILDING ELEMENT THAT IS ALTERED SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE. 11-4.13.5.
  
 5) SHEET A-6 INDICATES A NEW A/C ROOF TOP UNIT, PLEASE
 PROVIDE A CURB DETAIL AND ANCHORAGE AGAINST OVER
 TURNING AND SLIDDING. 1609.1.3.
  
 6) SHEET A6 & A7 DO NOT PROVIDE WHERE THE CEILING OR
 ROOF INSULATION WILL BE IN THE SECTION OF BUILDING WITH
 THE HIGHER FLAT ROOF? 13-404.1.ABC.1
  
 7) SHEET A-25 IS LABELED AS A PROPOSED "SECOND FLOOR"
 ACCESSIBILITY PLAN, IS THERE A SECOND FLOOR? 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 8)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.