2008-03-17 13:14:44REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ARCHITECTURAL PLANS REFER TO PAGE M-1 FOR MECHANICAL
 DETAILS. NO PAGE M-1 WAS FOUND IN PLANS. HOWEVER, THERE
 WERE TWO E-1 PAGES, ONE OF WHICH APPEARS TO BE INTENDED
 FOR MECHANICAL. PLEASE CORRECT SHEET NUMBERING AND
 REFERENCES ON PLANS.
  
 2. PLANS DO NOT SHOW ANY MEANS OR LOCATION FOR
 CONDENSATE DISPOSAL. CONDENSATE FROM ALL COOLING COILS
 AND EVAPORATORS SHALL BE CONVEYED FROM THE DRAIN PAN
 OUTLET TO AN APPROVED PLACE OF DISPOSAL. CONDENSATE
 SHALL NOT DISCHARGE INTO A STREET, ALLEY OR OTHER AREAS
 SO AS TO CAUSE A NUISANCE IN ACCORDANCE WITH FBCM
 307.2.1. SHOW MEANS AND LOCATION OF CONDENSATE DISPOSAL
 ON PLANS TO DEMONSTRATE COMPLIANCE WITH THIS SECTION.
  
 3. IS THIS PTAC UNIT CONSTRUCTED AND WITH ATTACHMENT
 DETAILS TO WITHSTAND ANTICIPATED WIND PRESSURES?
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING PER FBCM 301.13. PROVIDE
 TESTING OF APPLIANCE AND ATTACHMENT DETAIL TO
 DEMONSTRATE COMPLIANCE WITH THIS SECTION.
  