Plan Review Notes
Plan Review Notes For Permit 08030070
Permit Number 08030070
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2008-03-19 12:38:59*****DENIED*****
  
  
 1.THE ADDRESS SHOWN ON THE APPLICATION, 700 SOUTH
 ROSEMARY, DOES NOT CORRESPOND WITH THE ADDRESS SHOWN IN
 OUR PERMITTING SYSTEM (550 HIBISCUS STREET). FOR
 ADDRESSING CONCERNS OR MATTERS, CONTACT LILI URSU AT
 561-822-1239.
  
 2.THE ADDRESS OF THE SCOPE OF WORK LOCATION SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 3.CORRECT THE FOLLOWING ON SHEET A-1:*MISSPELLING
 OF ROSMARY, SHOULD BE ROSEMARY UNDER CITY PLACE KIOSK;
 *THE ZIP CODE SHOULD BE 33401 NOT 33405 AS LISTED.
  
 4.AMEND NOTE 2 ON SHEET A-1 TO READ:THE SCOPE OF
 WORK SHALL NOT INTERFERE/HINDER ACCESS TO OR EGRESS
 FROM THE SAID PROPERTY OR THE VICINITY THEREOF
 (INCLUDING STREETS, ALLEYS, FIRELANES, ETC.).
  
 5.DIRECTION ORIENTATION (NORTH, SOUTH, EAST, WEST)
 NEEDED FOR THE EXTERIOR ELEVATIONS ON SHEET A-2.
  
 6.SHOW/DIPLAY THE NUMERICAL ADDRESS ON THE EXTERIOR
 ELEVATION WHICH FRONTS SOUTH ROSEMARY AVENUE.
  
 7.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 8.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIAL IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 9.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE APPROPIATE PLAN SHEET
 EACH COMMENT WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722