Plan Review Notes
Plan Review Notes For Permit 08030070
Permit Number 08030070
Review Stop E
Sequence Number 1
Notes
Date Text
2008-03-08 18:47:36** DENIED REVIEW **
  
 1) NOTE: PLEASE KNOW AT THIS TIME THE CORRECT ADDRESS
 IS NOT AS APPLIED OR AS STATED ON PLANS. THELOCATION IS
 IN QUESTION AND THIS REVIEW HAS FORWARDED INFORMATION
 TO ADDRESSING REVIEWER FOR CORRECTIONS AND ADDRESS TO
 BE CORRECTED UNDER ACTUAL PCN.
 THIS IS A NEW FREE-STANDING STRUCTURE LOCATED ON A PCN
 OTHER THAN AS APPLIED. PLEASE KNOW THE PCN BASED ON
 PAPA AERIALS AND BASED ON THE LOCATION SHOWN ON PLANS
 SUBMITTED PLACES THIS IN PCN 74434321130020040.
 THIS WILL REQUIRE A NEW ADDRESS TO THIS STRUCTURE.
 PLEASE BE AWARE THIS STRUCTURE IS ACTUALLY BEING FED
 FROM A NEW PROPOSED SERVICE AND METER. PLEASE ALSO SEE
 PRINT OUT THIS REVIEWER HAS ATTACHED TO NOTES FOR
 AERIAL.
  
 2) NOTE: PLEASE BE SURE THE ADOPTED CODES PER FS 553.73
 AND FBC ARE REQUIRED TO BE STATED ON PLANS FOR RELEVANT
 DESIGN.
 PLEASE BE SURE THE FOLLOWING IS STATED ON PLANS FOR
 THIS REVIEWER.
 2004 FBC W/2007 REVISIONS.
  
 3) NOTE: PLEASE SEE COVER SHEET SPECIFICALLY STATES
 THERE IS TO BE A SHEET M-1 YET NO M SHEETS ARE IN
 SETS.
 PLEASE SEE THIS SAME COVER SHEET STATES THERE IS ONE
 E-1 YET THE SETS CONTAIN TWO E-1 SHEETS IN BOTH SETS.
 PLEASE COORDINATE ALL SHEETS AND ADJUST COVER SHEETS AS
 NEEDED ALONG WITH ADDRESSING AS STATED IN NOTE #1
 ABOVE.
 FAC 61G1-16.004, FBC 106.1, 106.5 ETC
  
 4) NOTE:PLEASE COMPLETE AL CIRCUITING AND COORDINATE
 WITH THE PANEL SCHEDULE AS SHOWN.
 MORE SPECIFICALLY 700.12 FOR EM LT. (EVEN AS NOTED).
  
 5) NOTE: PLEASE SEE PLANS FOR BUILDING DOES NOT SHOW
 THE LOCATION OF THE METER CAN AS SHOWN ON RISER.
 PLEASE COMPLETE LOCATION.
 110.26
 FBC 106.1.2
  
 6) NOTE: PLEASE SEE THE RISER IS MISSING THE REQUIRED
 EQUIPMENT GROUNDING CONDUCTOR AFTER THE FIRST MEANS OF
 DISCONNECT AS REQUIRED PER 250.24, 250.110, 250.122.
  
 7) NOTE: PLEASE CLARIFY RISER WHICH SHOWS THE GROUNDING
 ELECTRODE CONDUCTOR TO A METAL CWP YET THERE IS NO
 PLUMBING WATER RISER SHOWING ANY CWP OR WATER SYSTEM TO
 THIS STRUCTURE?
 PLEASE VERIFY.
 250.50
  
 8) NOTE: PLEASE SUBMIT THE AIC RATINGS FOR SERVICE
 EQUIPMENT AND MAIN. PANEL SCHEDULE DOES SHOW A PANEL
 RATING OF 4200 HOWEVER THIS OFFICE/REVIEWER KNOWS OF NO
 EQUIPMENT WHICH EXISTS ON THE MARKET AS OF THIS REVIEW
 WHICH IS 4200. PLEASE SUBMIT DOCUMENTS ON THIS OR
 VERIFY THE RATING.
 90.7, 110.3
  
 9) NOTE: PLEASE SEE 13-400.3.A, 13-415.2,NEEDS ENERGY
 CALCULATIONS
 NEED NOTES ON PLANS PER 13-413.1.ABC.2.1 AND .2.2.
  
 10) NOTE: PLEASE CORRELATE RISER AND PANEL. PANEL SHOWS
 3-#3 FOR FEEDERS YET THE RISER SHOWS 3-1/0?
 PLEASE SEE 240.4, 310.16.
 FBC 106.1.2 FOR COORDINATION.
  
 11) NOTE: PLEASE SEE THE D IN SQUARE BOX ON PLANS IS
 NOT LISTED ON THE SYMBOL LEGEND. THIS CAN BE ASSUMED
 HOWEVER THIS NEEDS TO BE LISTED PER DESIGNER.
 FBC 106.1.2 ADDITIONAL INFORMATION.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]