| 2008-03-07 17:31:40 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED IN |
| | ADDITION TO THE NOAS PROVIDED, FAC9B72. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 2.DECLARE TOTAL SF AREA OF THIS PROPOSED IMPROVEMENT. |
| | |
| | |
| | 3.IMPACT PROTECTION REQUIRED, FBC1609.1.4.USE OF |
| | REMOVABLE SHUTTERS ON COMMERCIAL PROPERTIES REQUIRES |
| | APPROVAL FROM THE BUILDING OFFICIAL.IF YOU PROPOSE TO |
| | USE REMOVABLE SHUTTERS, SUBMIT A HURRICANE INSTALLATION |
| | PLAN, SEE ATTACHED POLICY, ITEM 13.PROVIDE PRODUCT |
| | APPROVALS AND COMPLETE AN INSTALLATION SCHEDULE. |
| | |
| | 4.AN OUTSWING DOOR PRODUCT APPROVAL WAS SUBMITTED, |
| | INSWING SHOWN ON THE PLAN.PLEASE RESOLVE |
| | INCONSISTENCY. |
| | |
| | 5.PROVIDE ROOF TILE FOAM ADHESIVE PRODUCT APPROVAL, |
| | FAC9B72. |
| | |
| | 6.PROVIDE LOUVER PRODUCT APPROVALS, FAC9B72 AND |
| | SPECIFY DESIGN PRESSURES. |
| | |
| | 7.N/A (NO IMPACT FEES DUE PER GWEN/WILLY SWOPE). |
| | |
| | 8.PLEASE DECLARE GOVERNING CODE, INCLUDING 2007 |
| | SUPPLEMENTS/REVISIONS. |
| | |
| | 9.PROVIDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| | OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| | |
| | 10. PROVIDE A SITE PLAN WHICH SHOWS DISTANCE TO |
| | PROPERTY LINES AND ASSUMED PROPERTY LINES.SHOW |
| | COMPLIANCE WITH FBC TABLE 602. |
| | |
| | 11. SHOW ORIENTATION OF BUILDING ON EITHER THE FLOOR |
| | PLAN OR ELEVATIONS.NORTH IS NOT LABELED ON ANYTHING |
| | OTHER THAN THE SITE PLAN, WHICH DOES NOT SHOW ENOUGH |
| | DETAIL TO SHOW THE BUILDING ORIENTATION. |
| | |