| 2009-01-28 13:59:44 | ** DENIED PLANS/REVISIONS** |
| | |
| | 1) NOTE: SEE THE NOTES FROM THE PREVIOUS ELECTRICAL |
| | REVIEW. THE METHOD *C* CALCULATIONS ARE STILL BEING |
| | SUBMITTED. THESE MAY HAVE BEEN LEFT OVER FROM PREVIOUS |
| | REVIEW AND SHOULD BE REMOVED. |
| | THE NEW SUBMITTED METHOD *B* IS NOT SEALED BY THE |
| | DESIGN PROFESSIONAL AS REQUIRED. FS 471.025/ FAC |
| | 61G15-23.002, FBC 13-101 |
| | THE NEW THE METHOD *B* DOES NOT HAVE ANY INPUT DATA |
| | REPORT ATTACHED TO THE SUMMARY SHEETS. THIS WAS ALSO A |
| | COMMENT FROM THE PREVIOUS REVIEW. THE COMPLIANCE |
| | SUMMARY SHEET #2 STATES THE * INPUT DATA REPORT MUST BE |
| | SUBMITTED*. IN ORDER FOR CODE COMPLIANCE REVIEW TO TAKE |
| | PLACE THIS OFFICE MUST HAVE THE IDR TO REVIEW WITH THE |
| | SUBMITTED PLANS. |
| | |
| | 2) NOTE: THE BEAUTY CASES ARE NOT MANUFACTURED WITH |
| | LIGHTING INSTALLED FROM THE MANUFACTURE. BASED ON THE |
| | PRODUCT SHEETS SUBMITTED THESE ARE LIGHT FIXTURES ADDED |
| | TO GENERAL DISPLAY CASES/RACKS.13-415.2.ABC.1. THERE IS |
| | ALLOWANCES PERMITTED FOR ADDITIONAL LIGTHING FOR |
| | DSIPLAY AREAS HOWEVER SEE 13-415.2.B.2. PLEASE |
| | RE-CONFIGURE CALCULATIONS. |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | ** IMPORTANT ** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |