| 2008-12-24 14:11:22 | ** DENIED REVIEW OF REVISIONS** |
| | |
| | |
| | 1) NOTE: METHOD *C* FLA-COMM SUBMITTED DOES NOT CONTAIN |
| | ANY INPUT DATA REPORT. THE DESIGN WATTAGE IS HIGHER |
| | THAN ALLOWANCE PER FBC 13-415.2.ABC.1.1,.1.2, TABLE |
| | 13-415.2.C. |
| | PLEASE SEE PLANS WHICH CONTAINS METHOD *B* TABLE |
| | 13-415.2.B FOR COMPLIANCE WHICH HAS NOT BEEN UPDATED |
| | FOR CHANGES IN LIGHTING ON PLANS. |
| | PLEASE SEE 13-415.2.ABC.1. IT IS NOT PERMISSIBLE BY |
| | CODE TO USE MULTIPLE METHODS OF ENERGY CALCULATIONS TO |
| | TRY AND ACHIEVE CODE COMPLIANCE. |
| | |
| | ** PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR |
| | BEAUTY CASES IN WHICH EXEMPTION IN 13-415.2.ABC.1 IS |
| | BEING APPLIED. |
| | 110.3, 90.7. |
| | FBC 13-415.2.ABC.1.1, .1.2. |
| | |
| | 2) NOTE: PLEASE SUBMIT COMPLETE UPDATE AND REVISED |
| | PLANS FOR CODE COMPLIANCE. THE INPUT DATA REPORT AS |
| | STATED ON SHEET TWO OF THE SUBMITTED CALCULATIONS MUST |
| | ACCOMPANY THE SUBMITTED DOCUMENTS. NO REVIEW FOR CODE |
| | COMPLIANCE CAN BE ACHIEVED. |
| | FBC 106.1.1 FOR COMPLETE INFORMATION, CLARITY AND |
| | COORDINATION. |
| | CODE SECTIONS NOTED IN NOTE #1. |
| | |
| | 3) NOTE: FEE DUE FOR ENERGY CALCULATIONS SUBMITTED AS A |
| | SUBMITTAL. THIS IS ACTUALLY A REVISION TO BE REVIEWED |
| | AND COORDINATED WITH PLANS SUBMITTED. |
| | |
| | 4) NOTE: LETTERS SUBMITTED BY CITY PLACE AND RCC WERE |
| | NOT CORRECTLY NOTARIZED PER FS 117.05. PLACING THE |
| | NOTARY STAMP ON LETTER AND SIGNING IS NOT THE ONLY |
| | INFORMATION REQUIRED. LETTER FROM RCC DOES CONTAIN SOME |
| | MORE INFORMATION HOWEVER NOT ALL. A COMPLETED STATEMENT |
| | IN SECTION GIVEN CAN BE VIEWED ON LINE AT STATE |
| | WEBSITE. THE INFORMATION CAN BE FOUND IN SECTION |
| | 117.05(12)(B). |
| | |
| | |
| | **IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| | INTO TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |