| | ** DENIED REVIEW ** |
| | |
| | *** PLEASE KNOW THAT SUBMITTED DOCUMENTS ARE NOT |
| | COMPLETE AT THIS TIME. |
| | |
| | 1) NOTE: PLEASE SEE COVER SHEET A0.00 WHICH STATES |
| | NFPA-70 2005 AS THE SPRINKLER CODE WHEN NFPA-70 IS THE |
| | NATIONAL ELECTRICAL CODE. PLEASE SEE THIS SAME COVER |
| | SHEET STATES NFPA-101 2003 ALSO AS THE SPRINKLER CODE |
| | WHICH IS ALSO NOT POSSIBLE. THE 2003 NFPA-101 IS THE |
| | LIFE SAFETY CODE. |
| | PLEASE ADJUST ON COVER SHEET AND IN PLANS AS NEEDED. |
| | PLEASE BE SURE THE FOLLOWING RELEVANT CODES ARE STATED |
| | ON ELECTRICAL PLANS. |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE THE FLA-COM ENERGY CALCULATIONS |
| | SUBMITTED WHICH DO NOT CONTAIN ANY INPUT DATA REPORT. |
| | PLEASE SEE SHEET WHICH SPECIFICALLY STATES THE IDR MUST |
| | BE SUBMITTED. A REVIEW OF COORDINATION WITH THE ACTUAL |
| | ITEMS ON PLANS CAN NOT BE DONE AT THIS TIME WITHOUT |
| | THESE SHEETS. |
| | PLEASE BE SURE TO CORRELATE ALL LIGHTING ON PLANS WITH |
| | THE IDR WHEN RESUBMITTING. PLEASE BE SURE TO SEE |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3. |
| | PLEASE SEE 13-415.2.ABC.1( TRACK LTS, AND OTHER |
| | SPECIALTY LIGHTING SYSTEMS) |
| | ** PLEASE SEE ANY COMMENTS FROM OTHER TRADES WITH |
| | RESPECT TO THE ENERGY CALCULATIONS SUBMITTED. |
| | ** PLEASE BE SURE THE DESIGNER OF RECORD SIGNS DATES |
| | AND SEALS THE CERTIFICATION SHEETS ALONG WITH THE |
| | SIGNATURE FROM THE OWNER AGENT. |
| | FS 471.025, FBC 13-103.1.1.1 |
| | |
| | 3) NOTE: PLEASE SEE MISSING PRINTED NAME AND PRINTED |
| | LICENSE NUMBER IS LISTED ON TITLE BLOCKS AS REQUIRED |
| | PER FAC 61G15-23.002 |
| | ** THIS IS REQUIRED FOR ALL TRADES AND ALL REVIEWS |
| | WHETHER OR NOT COMMENT IS MADE BY THOSE OTHER TRADES. |
| | ** PLEASE KNOW FOR ANY SHEETS WHICH DO NOT NEED TO BE |
| | RE-PRINTED FOR COMMENTS, THIS MAY BE NEATLY PRINTED OR |
| | STAMPED ON TITLE BLOCKS. |
| | |
| | 4) NOTE: PLEASE SEE PLANS APPEAR TO BE SIGNED WITH |
| | INITIALS. PLEASE PROVIDE AN ORIGINAL NOTARIZED LETTER |
| | FOR SIGNATURE VERIFICATION. THIS WILL BE PLACED IN |
| | SIGNATURE FILE FOR FUTURE REFERENCE. |
| | FS 471.025 |
| | |
| | 5) NOTE: PLEASE SEE THE UNIT AS STATED ON TITLE BLOCKS |
| | IS SHOWN AS *B-5* WHEN THE ACTUAL SUITE/UNIT NUMBER AT |
| | LOCATION IS #108. PLEASE ADJUST TITLE BLOCKS. |
| | ** ONCE AGAIN FOR SHEETS WHICH MAY NOT NEED TO BE |
| | REVISED FOR COMMENTS THIS MAY BE NEATLY PRINTED OR |
| | STAMPED ON THE TITLE BLOCKS. |
| | FAC 61G1-16.004, 61G15-23.002, FBC ADMIN SECTION 106.5 |
| | |
| | 6) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4). PLEASE |
| | SEE THE MINIMUM LEVELS FOR ADA COMPLIANCE FOR ALL |
| | STROBE DEVICES SHALL MEET 75CD MINIMUM. PLEASE SEE THE |
| | LEVELS FOR THE HORN/STROBES INDICATE 75CD HOWEVER ALL |
| | STROBES ARE SHOWN AS 15CD WHICH IS WAY BELOW MINIMUM. |
| | PLEASE ADJUST. |
| | PLEASE SEE SOUND LEVELS ALSO WHICH MAY |
| | |
| | 7) NOTE:PLEASE ADJUST THE COLOR CODING FOR 277/480V |
| | SYSTEMS TO BROWN, PURPLE AND YELLOW. |
| | THE CITY OF WEST PALM BEACH AND ALL SURROUNDING |
| | JURISDICTIONS CONTAINED LOCAL AMENDMENTS FOR THE LAST |
| | 20PLUS YEARS WHICH HAD THE ABOVE COLORING CODING. EVEN |
| | AS THE TECHNICAL AMENDMENTS ARE NOT LONGER IN AFFECT |
| | KEEPING WITH ALL OTHER WIRING SYSTEMS ALREADY PRESENT |
| | IN THIS JURISDICTION AS WELL KEEPING WITH THE |
| | ELECTRICAL SYSTEMS ALREADY ON SITE THE ABOVE WILL BE |
| | REQUIRED.THE NEC ONLY PROVIDES ORANGE FOR A HIGH-LEG |
| | OPEN DELTA SYSTEMS, WHICH 277/480V IS NOT. AS THE NEC |
| | DOES NOT PROVIDE ANY COLOR CODING THIS IS PER AHJ AS A |
| | LIFE SAFETY, FIRE HAZARD, AND PROPERTY DAMAGE SAFETY |
| | MEASURE. |
| | 90.4. |
| | |
| | 8) NOTE: PLEASE VERIFY THE NOTE #3 IN SECTION 26 51 00 |
| | ON SHEET E01.1 WHICH STATES ** THE ENERGY POLICY ACT OF |
| | 1992*?? |
| | PLEASE KNOW THAT ANY ENERGY CODE COMPLIANCE MEASURES |
| | SHALL BE ACCORDANCE WITH THE FLORIDA ENERGY CODE |
| | CHAPTER 13. |
| | |
| | 9) NOTE: PLEASE SEE SECTION 26 27 28 FOR SWITCHING |
| | DEVICES DOES NOT APPLY. |
| | |
| | 10) NOTE: PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3 AND |
| | .1.4. |
| | PLEASE SEE THAT NOT ENOUGH INFORMATION WAS SUBMITTED |
| | FOR LIGHTING CONTROL SYSTEM. |
| | PLEASE SHOW ALL OVER RIDE DEVICE LOCATIONS AS REQUIRED. |
| | FOR EXAMPLE REAR ENTRANCE. OCCUPANT IS REQUIRED TO |
| | VISUALLY SEE THE LIGHTING BEING CONTROLLED OR MEETING |
| | THE EXCEPTION OF PILOT LIGHTS ETC. |
| | PLEASE PROVIDE TIMED SCHEDULING AND MAXIMUM OVER RIDE |
| | TIMES. |
| | PLEASE SHOW A LAYOUT OF ZONES REQUIRED. |
| | ** PLEASE KNOW AS NOTED ABOVE REVIEW FOR LIGHTING |
| | COMPLIANCE CAN NOT BE DONE.SEE NOTE ABOVE #2 |
| | |
| | 12) NOTE: PLEASE SEE THE CODE SECTIONS REFLECTED IN THE |
| | LOAD CALCULATIONS ARE NOT UNDER THE CURRENT NFPA-70 |
| | (NEC). |
| | PLEASE SEE SHOW WINDOWS ARE NOW IN 220.43. (PLANS |
| | REFLECT 220.12) |
| | |
| | 13) NOTE: PLEASE KNOW DEPENDING ON THE STRUCTURAL SCOPE |
| | OF WORK, THREE SETS OF PLANS MAY BE REQUIRED AS THIS IS |
| | A THRESHOLD BUILDING. THIS IS ONLY NOTED ONLY FOR |
| | INFORMATION. |
| | |
| | 14) NOTE: PLEASE VERIFY BUS RATING OF PANELS A, B AND C |
| | AS THESE ARE SHOWN AS 100A YET 42CIR PANELS. 110.3, |
| | 90.7. |
| | SUBMIT SPEC SHEET. |
| | FBC 106.1.2 |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |