| 2008-04-01 14:46:36 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 2.SHEET T1, INCLUDE 2007 REVISIONS/SUPPLEMENTS IN |
| | GOVERNING CODE. |
| | |
| | PLEASE ADD "2007 REVISIONS/SUPPLEMENTS" TO GOVERNING |
| | CODE.THIS ESTABLISHES WHICH VERSION OF THE FBC2004 IS |
| | TO BE USED ON THIS JOB AS IT HAS BEEN REVISED EACH |
| | YEAR, AND ON A DIFFERENT DATE EACH YEAR. |
| | |
| | 4.SPECIFY REQUIRED FIRE RATED WALLS.THERE ARE |
| | PENETRATION DETAILS BUT THE INFORMATION REGARDING WHICH |
| | DETAILS TO BE USED FOR THIS JOB IS NOT CLEAR. |
| | |
| | SHEET E7 WAS REVISED BUT REQUIREMENT IS STILL NOT |
| | CLEAR.YOU HAVE A 2 AND 3 HOUR FLOOR/WALL ASSEMBLY, |
| | TWO DIFFERENT FLOOR ASSEMBLIES, AND DETAILS 3 AND 6 |
| | STATE "FIREPROOF" WITHOUT FIRE RATING REQUIREMENT OR |
| | DETAIL REFERENCE.FROM THE PLAN, I CANNOT DETERMINE |
| | WHAT IS REQUIRED AND WHAT THE CONTRACTOR'S OPTIONS ARE. |
| | IF THIS IS A IA BUILDING, A 4 HOUR BEARING WALL |
| | REQUIRED, 3 HOUR FOR TYPE IB, FBC TABLE 601.SEE |
| | FBC712.3.1.SEE FBC712.4.1.NO T RATING WAS SHOWN, |
| | BUT SEE E3, A PENETRATION SHOWN BETWEEN THE PH |
| | ELECTRICAL ROOM AND FPL VAULT ROOM.IS THE FPL VAULT |
| | REQUIRED TO BE RATED?WHY IS THERE NO T RATING?IF |
| | THIS IS EXEMPTED IN THE CODE, PLEASE STATE EXEMPTION |
| | AND PROVIDE SPEC SHEETS FOR THE PRODUCT TO SHOW |
| | COMPLIANCE WITH THE EXEMPTION. |
| | |
| | PLEASE LABEL REQUIRED FIRE RESISTANCE AS REQUESTED SO |
| | THAT CODE COMPLIANCE CAN BE DETERMINED.INDICATE |
| | REQUIRED FIRE RESISTANCE FOR WALLS, ROOF, FLOORS. |
| | PLEASE ALSO DECLARE BUILDING CONSTRUCTION TYPE FBC |
| | CHAPTER 6. |
| | |