| Plan Review Notes For Permit 08030056 |
| Permit Number |
08030056 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-03-19 11:08:22 | | | | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL | | | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY | | | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL | | | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS | | | AMENDED. A PERMIT SHALL NOT BE ISSUED UNTIL FEES | | | AUTHORIZED UNDER SECTION 553.80, FLORIDA STATUTES, HAVE | | | BEEN PAID. 108.1 FBC. | | | | | | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY | | | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. | | | | | | 2} INDICATE IT ANY CABLE IS BEING RAN WITH THIS | | | APPLICATION AND IF ANY OTHER EQUIPMENT IS TO BE SET. IF | | | CABLE IS TO BE RAN , INDICATE THE ROUTING. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|